Burkert Type S030 User Manual

Page 10

Advertising
background image

36

→

Install the fitting on the pipe to comply with the
upstream and downstream distances defined by
standard EN ISO 5167-1 (see Fig. 3).

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows

at 90°

Pipe with 2 elbows at 90°

in 3 dimensions

Pipe with 1 elbow at 90°

or 1 T-piece

With pipe expansion

With pipe

reduction

Fig. 3: Upstream and downstream distances depending

on the design of the pipes.

English

37

→

Use a flow conditioner, if necessary, to obtain the best
accuracy.

→

Prevent the formation of air bubbles in the pipe (see
Fig. 4).

→

Ensure the pipe is always filled with liquid (see Fig. 5).

Correct

Correct

Incorrect

Incorrect

Direction of fluid flow

Fig. 4: Additional recommendations on installation

English

37

38

Correct

Incorrect

Correct

Incorrect

Fig. 5: Additional recommendations on installation

English

39

installing a fitting with weld ends

Follow the previously described general installation
recommendations.

note

the seal on the fitting with weld-end connections
may be damaged during welding.

→

Before welding the weld-ends, unscrew the 4 tigh-
tening screws.

→

Remove the sensor holder.

→

Remove the seal.

→

Weld the weld-ends.

→

After welding, correctly replace the seal in the
groove.

→

Replace the sensor holder.

→

Tighten the 4 screws in an alternating pattern, app-
lying a nominal tightening torque of 1,5 Nm.