Out (output) – setting the output signal – Burkert Type 8070 User Manual

Page 21

Advertising
background image

19

SettingandFunctions

9.4.3.

Out (Output) – setting the output signal

In this parameter, define whether the device is to work as a flow transmitter or a pulse divider.
setting as flow transmitter (4 - 20 mA):

When changing the unit (e.g. from liters to gallons) the limit values for the current output are not converted
automatically

→

Set the lower and upper limit values for the flow rate range associated to the 4-20 mA output, in the unit set within the
UNIT parameter.
The lower limit value is marked by an L (low) on the display and the upper limit value by an H (high).

setting as pulse divider (PULS):

→

Set the volume, in the displayed unit, for each pulse emitted on the NPN and PNP outputs.

Setting in the parameter:

* Order of value input:
1. Select the decimal point place

(each time the key is pressed: one position to
the left)

2. Set numerical values

Status display changes to "active"

set the flow rate range *

set the volume pro pulse, in the displayed unit *

Lower limit value

Upper limit value

select
flow
transmitter

select
pulse divider

mA

l

L = low

H = high

Fig. 13: Out – Setting the output; operation as flow transmitter or pulse divider

English