Installationandwiring

Type 8011

With regulating valve

Pipe with 2 elbows at 90°

in 3 dimensions

Pipe with 2 elbows

at 90°

Pipe with 1 elbow at 90° or 1

T-piece

With pipe expansion

With pipe reduction

50 x DN

5 x DN

40 x DN

5 x DN

25 x DN

5 x DN

20 x DN

5 x DN

18 x DN

5 x DN

15 x DN

5 x DN

Fig. 4: Upstream and downstream distances depending on the

design of the pipes.

If necessary, use a flow conditioner to improve measurement
precision.

Install the device in such a way that the paddle-wheel axis is
horizontal.

On an horizontal pipe, mount the device in such a way that the
paddle-wheel is downwards (Fig. 5).

Prevent the formation of air bubbles in the pipe in the section
around the device (Fig. 6).

Ensure that the pipe is always filled in the section around the
device (Fig. 7).

Fig. 5: Paddle-wheel downwards on an horizontal pipe

Correct

Correct

Incorrect

Incorrect

Fluid circulation
direction

Fig. 6: Air bubbles within the pipe

Correct

Incorrect