GeneralAire DH70 Dehumidifier User Manual

Read and save these instructions, Unit location, Form no. dh70 rev a

Advertising
background image

1

DH70 - Crawl Space, Attic or Basement
Whole House Dehumidifier
Installation & Owners Manual

Specifications

• Model: DH70
• Capacity: 70 pints/day, (3.25lbs./hr) @ 80°/60%RH
• Electrical: 110-120 VAC, 6.7 FLA Amps, 60 Hz, grounded
• Operating Return Air Temp. Range: 50°F min., 90°F max.
• Air Flow:

• 280 CFM without external ducting
• 235 CFM @ .30 IWG external static
• 195 CFM @ .50 IWG external static

• Refrigerant Charge: 17.5 oz. R-410A
• Duct connections: Return duct flange: 8” Round, Outlet 8” Round,
• Filter Size: High Efficiency (MERV 11): Pleated 11-3/4” X 11-3/4” X 2”
• Size (Clearance): 14” Height x 26” Width x 14” Depth, 12” minimum front or rear clearance for filter service.
• Weight: 65 pounds (Shipping Weight 80 pounds)

Read and Save These Instructions

FORM NO. DH70 REV A

Humidistat

27.25

23.25

13.00

12.75

13.75

13.00

Return

Supply

8"

8"

Filter Access

Filter Access

Filter Access

3/4" NPT Drain

3/4" NPT Drain Option

Factory Installed Plug

Grounded 120 V Power Cord - 90"

Service Access

Ajustable Legs 1/4"- 1"

Low Voltage Terminal

Humidistat

LEFT SIDE VIEW

TOP VIEW

FRONT VIEW

RIGHT SIDE VIEW

BACK VIEW

DH 70

Read the installation operation and maintenance instructions carefully before installing and using this unit.

Proper adherence to these instructions is essential to obtain maximum benefit from the DH70 system.

Installation contrary to these guidelines or lack required maintenance will void warranty.

Unit Location

The DH70 can be installed in a variety of locations to meet the
owner’s needs as listed below. In all cases keep the following
cautions in mind:

• The unit is designed to be installed indoors in a space that is

protected from rain, flooding and/or other forms of excess water.
Unit is not designed to be exposed to chlorinated pool conditions
or spaces where unit will be exposed to corrosive chemicals or
conditions.

Install the unit with space to access the front panel for

maintenance and service. Also allow easy access to the filter

cover panel.

DO NOT INSTALL THE UNIT WITH THE FRONT

PANEL OR FILTER COVER PANEL INACCESSIBLE.

• Avoid discharging the air directly at people, over the water in pool

areas, or other areas or objects where dehydration or evaporation
of moisture is not desired.

• If used near wet areas, be certain there is NO chance the unit could fall into the water or be splashed and that it is

wired into a GROUND FAULT INTERRUPTER protected circuit (see local codes for other requirements).

• A secondary drain pan

MUST be placed under the unit if installed above a living area or above an area where water

leakage could cause damage (see local codes for other requirements).

• DO NOT locate the DH70 directly on structural members where noise or vibration may be objectionable. The DH70

is equipped with adjustable support feet to raise and level the unit from the mounting surface, these adjustable feet
should be utilized to provide improved drainage from the drain pan and should be adjusted to tilt slightly toward the
drain utilized.