Wiring, Unit schematic – GeneralAire DH70 Dehumidifier User Manual

Page 4

Advertising
background image

4

F. Installation in a Structure with No Existing Forced Air HVAC System (Whole House Dehumidification)

When installing the DH70 in a structure that does not have a forced air HVAC system, a single return for the DH70
should be installed in central open area of the structure.

DO NOT locate the return in a bathroom or a kitchen. The

supply of the DH70 should be located in the remote areas of the structure (such as bedrooms, den, etc.). By ducting
this way, the air inside the structure will circulate through the DH70 to be filtered and dehumidified. 5” diameter duct is
recommended for branches to the bedrooms, 6” diameter duct is recommended for branches to larger areas.

G. Installation in a Sealed Crawl Space or Sealed Attic (Spot Dehumidification)

When installing the DH70 in sealed crawlspace or sealed attic, a single return for the DH70 should be installed in
central open area of the structure. If the area is open without partitions return ducting is not necessary. Supply
ducting is recommended to enhance the performance of the system, a minimum length of supply duct, 3’ to 6’ will
aid in air distribution. If the area(s) being served are divided by walls or partitions, a supply and return duct system is
recommended. In all cases sound duct design practices must be followed such as those provided in ACCA manual “D”,
or ASHRAE’s “Fundamentals of Air System Design”.

Wiring

Unit Schematic

Freeze

Stat

Blower Motor

Compressor

S

R

C

Fan Relay

Compressor

Run Capacitor

120 Volt 60Hz 15 Amp

1 Phase Power Supply

Compressor Relay

7

8

GT

GF

RF

D

G

C

R

Humidistat / Ventilation Control

Blower InterLock Connections (Low Voltage)

Fan Coil / Air Handler

Control Thermostat (Typ)

G

R

W

Y

G

R

W

Y

Existing Field Supplied

Control Wiring (Typ)

Field Supplied Control Wiring

Disconnect Existing Control Wiring

From Fan (G) Control Terminal

Reconnect to Blue Wire From DVA

Connect Brown Wire From DVA

To Fan (G) Terminal

Org Brn

Blu

Wiring Connections Line and Low Voltage

GT

GF

RF

Red

Wht

Gry

Yel

Org

Brn

Blu

3

5

1

4

6

2

Blower Motor

Run Capacitor

7

8

3

5

1

4

6

2

Low Voltage Terminal

Transformer

Humidistat

OPTIONAL

*

*

*

Remove Jumper If Fan Control Is Used

Molex 50-84-1040