Error codes – Aquacal 35 EN User Manual

Page 6

Advertising
background image

Page 5

SECTION 5 - TROUBLESHOOTING

ERROR CODES

SYMPTOM

RULE OUT

RESOLUTION

"FLO"

Insufficient water flow
through heater or
circulation pump is off

Insufficient Water Flow

Step 1:
Confirm water pump is on and water valves are in the correct position to allow
water to flow through Heat Pump. If error persists, proceed to next step.

Filtration Dirty

Step 2:
Confirm filtration system is clean. Backwash if needed. If error persists,
proceed to next step.

Possible Water
Pressure Switch

Step 3:
Request Service

“CEr” Error

Communication Fault

N/A

Request Service

“CSE” Error

Control System Error

N/A

Request Service

“dPC” Error

Defrost Sensor Shorted

N/A

Request Service

“dPO” Error

Defrost Sensor Open

N/A

Request Service

“FS” Error

Unit in defrost mode.

Normal defrost mode

Step 1:
If error persists after air temperature is over 50° F, request service.

“HP” Error

High Pressure.

Insufficient Water Flow

Step 1:
Confirm water pump is on and water valves are in the correct position to allow
water to flow through Heat Pump. If error persists, proceed to next step.

Filtration Dirty

Step 2:
Confirm filtration system is clean. Backwash if needed. If error persists,
proceed to next step.

Possible Refrigerant
Issue

Step 3:
Request Service

“HP5” Error

Equipment has
registered high pressure
five times and locked.

Insufficient Water Flow
and/or Filtration Dirty

Step 1:
Follow steps outlined in “HP” error, then reset circuit breaker to clear error. If
error persists, request service.

“LP” Error

Refrigerant Issue

N/A

Request Service

“LP5” Error

Refrigerant Issue

N/A

Request Service

“OTA”

Over Temperature
Alarm

Temperature over
110° F (Unit Locked)

Other heating
equipment

Check if alternate heater (such as a solar heater) is heating water leading to
heat pump. If “yes”, turn off alternate heater and check if error clears. If error
persists, request service.

“PC” Error

Water Temperature
Sensor Shorted

N/A

Request Service

“PO” Error

Water Temperature
Sensor Open

N/A

Request Service

Table 8