Instrument air exposed to outdoor freezing tem-
per a tures must be desiccant dried. Re frig er at ed
drying is not ad e quate.

Instrument air exposed to indoors and/or no-freezing
tem per a tures is recommended to be re frig er ant
dried as a minimum.

If the air supply is at a remote location, and can
not be practically dried and bears oil (i.e. plant air),
co a lesc ing fi lters must be utilized to re move as
much oil and water as possible, as well as par ti cles
over 15 mi crons size.

Figure 4: Recommended Thermal Well (Opt. 64) Installation

TABLE 1

Controller

Model 764T

ISA to

Port

Action

Direct

Reverse

A

Exhaust

Supply

B

Supply

Exhaust

PROCESS

TEMPERATURE

Increase in
temperature
increases output
signal

Increase in
temperature
decreases output
signal

TABLE 2

Controller

"Heating Applications"

IAS to

Port

Actions

Control Valve

Controller

A

ATO-FC
(Reverse)

Reverse
Increase in temperature
decreases output signal.
Valve "fails" to "cooler"
process temperature.

B

ATC-FO
(Direct)

Direct
Increase in temperature
increases output signal.
Valve "fails" to "hotter"
process temperature.

B

"Cooling" Applications

Actions

ATO-FC
(Reverse)

Direct
Decrease in temperature
decreases output signal.
Valve "fails" to "hotter"
process temperature.

A

ATC-FO
(Direct)

Reverse
Decrease in temperature
increases output signal.
Valve "fails" to "cooler"
process temperature.

11.

12.

13.