Preparing for Operation

56

SIPART PS2 Manual

A5E00074631-01

3.5 Pneumatic Connection

!

WARNING
For reasons of safety, the pneumatic power may only be supplied after

assembly when the positioner is switched to operating level P manual

operation with electrical signal applied (as--delivered state, see figure

4-4, page 76).

.

NOTE
Note the air quality! Oil--free industrial air, solid content < 30 μm, pressure

dew point 20 K below the lowest ambient temperature.

-

Connect a manometer block for supply air and actuating pressure if

necessary.

-

Connection by female thread G 1/4 DIN 45141 or 1/4” NPT:
P

Z

Supply air 1.4 to 7 bar

Y1

actuating pressure 1 for single-- and double--acting

actuators

Y2

actuating pressure 2 for double--acting actuators

E

exhaust air outlet (remove silencer if necessary)

see figure 2-3 and 2-4, page 18.

-

Safety position when the electric power supply fails:
single action:

Y1

deaerated

double action:

Y1

Max. Actuating pressure

(supply air pressure)

Y2

deaerated

-

Connect actuating pressure Y1 or Y2 (only in double--acting

actuators) according to the desired safety position.

-

Connect supply air to P

Z

.

.

NOTE
In order for spring--loaded pneumatic actuators to be able to reliably

exploit the maximum possible actuating path, the supply pressure must

be sufficiently greater than the maximum required final pressure of the

actuator.