IOM-DA0

3

9. Develop

system

fl ow to a level near its expected

normal rate, and reset the regulator set point by
adjusting the loading system pressure control
setpoint to the desired outlet pressure level.

SECTION VI

10. Reduce system fl ow to a minimum level and

observe pressure set point. Outlet pressure
will rise from the set point of Step 9 for a Model
DA0. The max i mum rise in outlet pres sure on
de creas ing fl ow should not exceed the 10%. If
it does, consult factory.

VI. SHUTDOWN

1. Shutoff inlet block valve.

2. Shutoff auxiliary loading pressure source, if sup-

plied. For spring loaded pilots, relax the range
spring by turning the adjusting screw CCW until
adjusting screw is removed.

3. Allow

suffi cient time for the line pressure down-

stream of the inlet block valve to bleed down.

4. Shutoff the outlet block valve.

5. Relieve the trapped upstream and downstream

pressure and loading pres sure.

6. The regulator may now be removed from the

pipe line or disassembled for inspection and pre-
ven ta tive main te nance while in-line.

VII. MAINTENANCE

A. General:

Item No.

Part Description

7

...................................................................................Nut

10 ......................................................................Stop Plate

13

....................................................Guide

Bearing/Piston

14 ...............................Lower and Upper Static Stem Seal

15 .......................................................... Cage O-ring Seal

16

............................................................................ Wiper

17

............................................................... Wiper

Washer

19

............................................................................. Cage

20

..............................................................................

Plug

21

...................................................................... Seat

Ring

27 ....................................................... Dynamic Side Seal

SECTION VII

1. The regulator may be serviced without

re mov ing the regulator from pipeline. The
reg u la tor is designed with quick-change trim
to simplify maintenance.

2. Record the nameplate information to req-

ui si tion repair parts for the regulator. The
in for ma tion should include: size, Product
Code and Serial Number.

3. Refer to Section X for recommended repair

parts. Only use original equipment parts
sup plied by Cashco/KM for re build ing or
re pair ing reg u la tors.

4. Owner should refer to owner's procedures

for removal, handling, cleaning and disposal
of nonreuseable parts, i.e. gaskets, etc.

5. The Inner Trim is re moved and replaced in

the body ( 23) as an assemblage of parts.
The Inner Trim Assembly, here in af ter called
ITA, consists of the following parts:

WARNING

SYSTEM UNDER PRESSURE. Prior to per form ing any
maintenance, isolate the reg u la tor from the system and
relieve all pressure. Failure to do so could result in per-
sonal injury.

Figure 1: Dynamic Side Seals