TEST PROCEDURE

1. Pressure at gauge “A” should simulate the actual pres-

sure to be used for the application.

2. Crack open valve “B”.
3. Crack open valve “A” while observing the pressure at

gauge “B”.

4. Slowly close valve “B” and watch gauge “B”. If the pres-

sure at gauge “B” is lower than desired, loosen the jam
nut and increase outlet pressure. If the gauge “B” pres-
sure is higher than desired, crack open valve “B” and
back off the adjusting screw (counter clockwise) until
the desired pressure is reached. Tighten the jam nut.

5. Open and close valve “B” a few times to insure proper

setting and operation.

Valve Concepts, Inc.

3644 Westchase Drive

Houston, TX 77042-5224
PH (713) 271-7171
Fax. # (713) 271-0153
www.valveconcepts.com
email: [email protected]
Printed in U.S.A. Model 1088 IOM