F–stop, R–stop, H–stop – CONTREX CX-1010 User Manual

Page 17

Advertising
background image

Page 15

F–Stop

(J6 pins 1,3)
Digital Input 0

F-STOP is a momentary input. When it is opened, the
CX–1010 commands a zero speed immediately and
ignores the specified deceleration rate. However,
F–STOP does not hold zero speed or position (drive
disabled). As a momentary input, F-STOP is internally
latched and does not need to be maintained open by an
operator device.

R–Stop

(J6 pins 2, 3)
Digital Input 1

R–STOP is a momentary input. When it is opened, the
CX–1010 ramps to a zero speed command at the
specified deceleration rate. However, R–STOP does
not hold zero speed after the deceleration ramp has
been completed (drive disabled) . As a momentary
input, R–STOP is internally latched and does not need
to be maintained open by an operator device.

H–Stop

(J6 pins 3, 4)
Digital Input 2

H–STOP is a momentary input. When it is opened, the
CX–1010 ramps to a zero speed command at the
specified deceleration rate. In addition, H–STOP holds
zero speed after the deceleration ramp has been
completed (drive enabled). As a momentary input,
H–STOP is internally latched and does not need to be
maintained open by an operator device.

Figure 13 F–Stop

F-STOP

1

3

J6

DI_0

COM

Figure 14 R–Stop

R-STOP

2

3

J6

DI_1

COM

H-STOP

3

4

J6

COM

DI_2

Figure 15 H–Stop