4 network cabling – CTI Products MCN RCD System Overview User Manual

Page 32

Advertising
background image

MCN System Manual

Hardware Installation

CTI Products, Inc.

68-10833-120

28

7.4 Network

Cabling

MCN modules communicate over a network cable. Specifications for network
cabling are the following:

• 4 pair level IV or V unshielded, 24 AWG, twisted pair cable (EIA/TIA

568B).

• Maximum of 20 modules can be connected together in a segment.

• Maximum cable length is 1200 feet.

• Straight through connections.

Figure 11 shows one side of the network cable. This diagram details the pinout
and twisted pair configuration of the cable.

CA-80042-100

1
2
3

7
8

TOP VIEW

OF CONNECTOR

4
5
6

DATA +
DATA -
+POWER

NC

NC

-POWER
-POWER
+POWER

Figure 11 - MCN Cable Pinout

When cabling your system, daisy-chain the modules together and insert a network
terminator into the unused port of the first module and the unused port of the last
module in the chain. An example of what the terminator looks like is shown in
Figure 12.

CA-80025-100

100 ohm 1/8 WATT
RESISTOR

Figure 12 - MCN Network Terminator

Use of standard length cables from CTI Products is highly recommended to
provide best system performance. Standard lengths up to 100 feet can be
combined with cable couplers to create desired length cables. See section 1.3 for

Advertising