Dip switch configuration, Dip switch "a, Dip switch "b – Controlled Products Systems Group RAM3200 User Manual

Page 14

Advertising
background image

www.ramsetinc.com

RAMSET

12

RAM 3000 • 3100 • 3200

dip SwiTCh CONFigurATiON

“Intelligate” Control Board

DIP SWITCH "A"

Dip Switch "A" 1, 2 & 3;

AUTOMATIC TIMER TO CLOSE GATE

‘0’ is “OFF” ‘1’ is “ON”

Switch 1 2 3 Gate Open Duration:

1 1 1 60 seconds
1 1 0 45 seconds
1 0 1 30 seconds
1 0 0 15 seconds
0 1 1 10 seconds
0 1 0 05 seconds
0 0 1 00 seconds
0 0 0 disabled - command required to close

Dip Switch "B" 1; Not in use at this time.

Leave in the ‘Off’ position.

Dip Switch "B" 4,5,6 & 7; Not in use at this time.

Leave in the ‘Off’ position.

Dip Switch “A” 4 - 1/2 HP ERD

Dip switch A4 works with Dip switch B8

DIP A4 B8 Sensitivity
OFF OFF Most Sensitive
ON OFF 1/2 Hp—Medium Sensitivity
OFF ON

3/4 Hp—Medium Sensitivity

ON

ON

Least Sensitive

DIP SWITCH "B"

Dip Switch "B" 2; “PRE WARN”

Used with JP2 “Relay Connections” : pins 7 & 8.

Triggers a relay, for an alarm or light (not included), for 3 sec-

onds before the gate will move in any direction.

Sw.

Function:

ON Triggers the relay on JP2 pins 7 & 8 for 3 seconds.

OFF

Regular working conditions

Dip Switch "B" 3; “CONSTANT WARN”

Used with JP2 “Relay Connections” : pins 7 & 8.

Triggers a relay, for an alarm or light (not included), to be ac-

tive anytime the gate is in motion.

Sw.

Function:

ON Triggers the relay on JP2 pins 7 & 8 while the gate

is moving

OFF

Regular working conditions

Dip Switch “B” 8 - 3/4 HP ERD

Dip switch B8 works with Dip switch A4

DIP A4 B8 Sensitivity
OFF OFF Most Sensitive
ON OFF 1/2 Hp—Medium Sensitivity
OFF ON

3/4 Hp—Medium Sensitivity

ON

ON

Least Sensitive