Wiring installation – Custom Electronics AOV Multi Zone User Manual

Page 14

Advertising
background image

8) Wiring Installation

Upon installation maximum cable lengths must be adhered to, use the following table to calculate the
maximum cable lengths, taking in to account the cross section of the cables.

Cross Section

3 wire

5 wire

3 wire

5 wire

3 wire

5 wire

1.5mm

2

1.5mm

2

2.5mm

2

2.5mm

2

4mm

2

6mm

2

Actuator current

Amps

2 wires in
parallel

2 wires in
parallel

1

105.00m 210.00m 175.00m 350.00m 280.00m 420.00m

2

52.50m 105.00m 87.50m 175.00m 140.00m 210.00m

3

35.00m 70.00m 58.33m 116.67m 93.33m 140.00m

4

26.25m 52.50m 43.75m 87.50m 70.00m 105.00m

5

21.00m 42.00m 35.00m 70.00m 56.00m 84.00m

6

17.50m 35.00m 29.17m 58.33m 46.67m 70.00m

7

15.00m 30.00m 25.00m 50.00m 40.00m 60.00m

8

13.10m 26.20m 21.80m 43.75m 35.00m 52.50m

(For ambient temperatures of 25

°C)


If the above table does not correspond to your system design the following calculations can be used for
cable length:






The cable length from the actuator to junction box should not exceed 10m,

Maximum permissible voltage drop in the cable: 2.5V

Max. cable length = permissible voltage drop (2.5) x conductivity of copper (56) x Cable cross-sectional area (A)
Max.

Actuator

current

total

(I)

x2