Laurel Electronics LAUREATE SERIES 2 DIGITAL PANEL METER User Manual

Page 36

Advertising
background image

36

KEYSTROKES FOR SETUP

If the MENU

key does not work, see Section 9 “Enabling & Locking Out Menu Items.”


Press Menu
Select Key

Press Digit
Select Key

Press Value Select
Key

_-

rtd

_

RTD

..

d °F

-

Pt100 RTD, DIN alpha .00385, °F

..

d

°C

.

Pt100 RTD, DIN alpha .00385, °C

..

A

°F

-

Pt100 RTD, ANSI alpha .003902, °F

..

A

°C

-

Pt100 RTD, ANSI alpha .003902, °C

.

ni

°F

-

Ni120 RTD, alpha .00672, °F

.

.

ni

°C

-

Ni120 RTD, alpha .00672, °C

.

Cu

°F

-

Cu10 RTD, alpha .00427, °F

.

Cu

°C

-

Cu10 RTD, alpha .00427, °C

_

InPut

Selection of signal
input type & range

OHnnS

Ohmmeter

Set decimal point
under

dEc.Pt

..

20

-

0 to 20.000 ohms

..

200

.

0 to 200.00 ohms

..

2000

-

0 to 2000.0 ohms

.

20000

0 to 20000 ohms

200.00

0 to 200.00 kohm

0

0_00

Display selection with
scale factor of 1.

0

0.1° RTD or 4-1/2 digits for ohms

1

5-digit remote display (±99,999)

2

0.01° RTD, 4-1/2 digit ohms count by 10

3

1° RTD or 3-1/2 digits for ohms

00 _00

Power line frequency

0

Noise minimized for 60 Hz

1

Noise minimized for 50 Hz

00_ 00

Scaling method

0

Scale and offset method (RTD & ohms)

1

Coordinates of 2 points (ohms)

2

Reading coordinates of 2 points (ohms)

SEtuP

Meter Setup

00_00

Control inputs 1 & 2:

True = logic 1 (0V or
tied to digital ground)
False = logic 0 (5V or
open)

0

1 = Reset, 2 = Meter Hold

1

1 = Function Reset, 2 = Peak or Valley

2

1 = Hold, 2 = Peak or Valley Display

3

1 = Hold, 2 = Tare

4

1 = Peak or Valley Display, 2 = Tare

5

1 = Tare, 2 = Reset

6

1 = 0, 2 = 0, decimal point 1= XXXXX

1 = 1, 2 = 0, decimal point 1 = XXXX

.

X

1 = 0, 2 = 1, decimal point 1 = XXX

.

XX

1 = 1, 2 = 1, decimal point 1 = XX

.

XXX

7

1 = 0, 2 = 0, decimal point 2 = XXXX

.

X

1 = 1, 2 = 0, decimal point 2 = XXX

.

XX

1 = 0, 2 = 1, decimal point 2 = XX

.

XXX

1 = 1, 2 = 1, decimal point 2 = X

.

XXXX