Formula #2, Formula #1, Calibration – Liquid Controls IT150N User Manual
Page 6
 
Sponsler, Inc.
IT150N Remote Totalizer
pg
6
DOC# MN-150N-B
 
 
 
 
 
 
CALIBRATION
 
 
Sensitivity 
 
The sensitivity adjust R1 is located on the IT150I (Input and Analog) P.C.B. The amplitude of the signal 
generated by the turbine is proportional to the rate of flow; therefore, sensitivity should be adjusted at the 
lowest usable flow rate. Rotate R1 completely counterclockwise then slowly rotate R1 clockwise until the 
display correctly responds then increase R1 slightly clockwise. The nominal R1 position is with the arrow 
indicating 11 o’clock. 
 
 
FIGURE 2
 
 
 
 
 
 
 
 
 
 
 
 
Calibration Factor 
 
The calibration factor is derived from the turbine’s K-Factor (Pulses per gallon or other desired 
engineering unit). 
C.F. =
Engineering units
K-Factor
 
EXAMPLE 1: K-Factor = 250 pulses per gallon 
 
Engineering Units = gallons
∴ C.F. = 1/250 = .004000
On the Factoring P.C.B.:
Set S6 #3 ‘ON’ (
↓ Position) for ÷ 100 (moves decimal point right 2 places)
Set S2@4, S3, 4, 5@0 (.4000)
Set S1 in ‘0’ position (.4000) (On the IT150I P.C.B.)
 
The electrical accuracy can be verified by injecting a stable frequency @ TB2-1,2 on the Mounting 
P.C.B. and incorporating the following formula: 
Total =
F x T x C.F.
D
 
 
Where F = Frequency in Hz (
)
 
 
T = Time (Duration) of test in seconds
C.F. = Calibration Factor as entered in S1-S5
D = Divider as entered in S6
Frequency =
K-Factor x Flowrate
60
Formula #1
Formula #2