Electrical specifi cations – MaxPower Corp FirstLine P User Manual
Page 4

Electrical Specifi cations
www.stacoenergy.com
Electrical Data
UPS Power (kVA)
65
80
100
125
160
200
250
INPUT
Nominal voltage
480Vac 3 phase, 3 or 4-Wire + Grd. (208V Optional with IP Transformer)
Nominal voltage range without battery contribution
-10%, +15%
Voltage range in battery mode
-40%, + 15%
Input frequency range
From 45 to 65Hz
Nominal current absorbed (480V)
78.2
94
118
147
188
235
294
Maximum current absorbed at full load
and battery recharging (Amps)
90
109
136
168
212
265
331
Power factor at nominal voltage (480 V) and
battery charged from 25% to 100% of the load
>0.99
Current Harmonic distortion (THDi)
(with mains distortion <2%)
• load 100%
• load 75%
• load 25÷50%
d 3%
d 5%
d 8%
Progressive rectifi er (Walk-in)
from 0 to 30 seconds (confi gurable)
from 0 to 120 sec. (confi gurable)
Delay of Progressive start of rectifi er
(Power Walk-in delay timer)
from 0 to 120 seconds (confi gurable)
D.C. INTERMEDIATE CIRCUIT
Number of cells
240
Float voltage (2.26 V/el, can be calibrated) – Vdc
542
Recharge Voltage (2.34 V/el, can be calibrated) – Vcc
561
542
Maximum output voltage (Vcc)
600
End of discharge voltage
Vcc (1.6 V/el, can be calibrated) – Vcc
384
Ripple current with recharged battery (%)
Approx. 0
Maximum DC current at cutoff voltage (Amps)
159.5
196
236
296
383.0
478.7
598.4
Maximum current to charge battery with 240 cells
(mains voltage 480V )
●
Load 100%
●
Load
d 70%
16
49
20
60
24
76
30
96
36
110
45
145
56
180
INVERTER
Factor of power reduction for 0.9 o/p leading
power factor
0.89
Nominal voltage
480Vac 3 phase, 3-Wire + Grd. (208V Optional with OP Transformer)
Nominal frequency
60Hz
Nominal voltage
+5%, -10%
Static variation
± 1%
Dynamic variation
± 5%
Resistor time within ± 1%
20ms
Crest Factor
3:1
Voltage distortion with linear load
1% (typical), 2% (max)
Voltage distortion with non-linear load
< 3%
Frequency stability with synchronized inverter
to the by-pass network.
± 2% ( ± 1% to ± 6% from control panel)
Frequency stability with not synchronized
inverter to the by-pass line
± 0.05%
Speed of frequency variation
1Hz/sec
(parallel units can be calibrated from 0.1 to 1Hz/s)
Phase voltage asymmetry with balanced
and unbalanced load.
d 1%
Phase displacement of the voltages with
balanced and unbalanced loads.
120 ± 1 °el
Overload in referred to the nominal power
●
Three phase
●
Single phase
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
200% for 7 seconds
200% for 6 seconds
Short circuit Current
●
Phase / Phase
●
Phase / Neutral
180% for 1 second
300% for 1 second
Inverter effi ciency
94%