Electrical specifi cations – MaxPower Corp FirstLine P User Manual

Page 4

Advertising
background image

Electrical Specifi cations

www.stacoenergy.com

Electrical Data

UPS Power (kVA)

65

80

100

125

160

200

250

INPUT
Nominal voltage

480Vac 3 phase, 3 or 4-Wire + Grd. (208V Optional with IP Transformer)

Nominal voltage range without battery contribution

-10%, +15%

Voltage range in battery mode

-40%, + 15%

Input frequency range

From 45 to 65Hz

Nominal current absorbed (480V)

78.2

94

118

147

188

235

294

Maximum current absorbed at full load
and battery recharging (Amps)

90

109

136

168

212

265

331

Power factor at nominal voltage (480 V) and
battery charged from 25% to 100% of the load

>0.99

Current Harmonic distortion (THDi)
(with mains distortion <2%)
• load 100%
• load 75%
• load 25÷50%

d 3%

d 5%

d 8%

Progressive rectifi er (Walk-in)

from 0 to 30 seconds (confi gurable)

from 0 to 120 sec. (confi gurable)

Delay of Progressive start of rectifi er
(Power Walk-in delay timer)

from 0 to 120 seconds (confi gurable)

D.C. INTERMEDIATE CIRCUIT
Number of cells

240

Float voltage (2.26 V/el, can be calibrated) – Vdc

542

Recharge Voltage (2.34 V/el, can be calibrated) – Vcc

561

542

Maximum output voltage (Vcc)

600

End of discharge voltage
Vcc (1.6 V/el, can be calibrated) – Vcc

384

Ripple current with recharged battery (%)

Approx. 0

Maximum DC current at cutoff voltage (Amps)

159.5

196

236

296

383.0

478.7

598.4

Maximum current to charge battery with 240 cells
(mains voltage 480V )

Load 100%

Load

d 70%

16
49

20
60

24
76

30
96

36

110

45

145

56

180

INVERTER
Factor of power reduction for 0.9 o/p leading
power factor

0.89

Nominal voltage

480Vac 3 phase, 3-Wire + Grd. (208V Optional with OP Transformer)

Nominal frequency

60Hz

Nominal voltage

+5%, -10%

Static variation

± 1%

Dynamic variation

± 5%

Resistor time within ± 1%

20ms

Crest Factor

3:1

Voltage distortion with linear load

1% (typical), 2% (max)

Voltage distortion with non-linear load

< 3%

Frequency stability with synchronized inverter
to the by-pass network.

± 2% ( ± 1% to ± 6% from control panel)

Frequency stability with not synchronized
inverter to the by-pass line

± 0.05%

Speed of frequency variation

1Hz/sec

(parallel units can be calibrated from 0.1 to 1Hz/s)

Phase voltage asymmetry with balanced
and unbalanced load.

d 1%

Phase displacement of the voltages with
balanced and unbalanced loads.

120 ± 1 °el

Overload in referred to the nominal power

Three phase

Single phase

110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute

200% for 7 seconds

200% for 6 seconds

Short circuit Current

Phase / Phase

Phase / Neutral

180% for 1 second
300% for 1 second

Inverter effi ciency

94%