Micromod Micro-DCI: 53MC5000 MicroLink User Manual
Page 23

8.2 CONFIGURING THE 53MC5000 PCS GATEWAY PARAMETERS
To activate gateway operation in a 53MC5000 PCS, set the specified datapoint parameters (see IB
53MC5000, Section 3) as follows:
1. Set INSTRUMENT ADDRESS (IA) (B01) to a unique value for the combined Datalink/Mi-
crolink network.
2. Set BAUD (B02) to the appropriate data transfer rate index value of the Datalink net-
work:
B02
Baud Rate
9
28,800
8
14,400
7
19,200
6
9,600
5
4,800
4
2,400
3
1,200
2
600
1
300
0
110
3. Set MICROLINK COMM MODE (B448) to the appropriate data transfer rate index value
of the MicroLink network:
Mode
Mbit/s
0
2
1
1
2
0.5
3
0.25
4. Set NO PARITY (L256) as required for the Datalink network (default is EVEN PARITY).
0 for EVEN PARITY serial byte protocol.
1 for NO PARITY protocol.
5. Set DATALINK DISABLE (L257) to 0.
6. Set NO BYTE STUFF (L258) to 0.
7. Set GATEWAY MODE (L260) as required:
0 for Datalink responder mode operation.
1 for Datalink interrogator mode operation.
8. Set GATEWAY ON (L259) to 1.
Section 8. Configuring the 53MC5000 PCS as a Gateway
24