Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller FLEXIBLE CONTROL STRATEGIES User Manual
Page 23

Logic Functions
FC
OUTPUT
FC
OUTPUT
0
A
4
A OR NOT B
1
A OR B
5
A AND NOT B
2
A AND B
6
J-K LATCH
3
A XOR B
7
D LATCH
Invert output if FC = FC + 128
Expanded Logic Functions
INPUTS
OUTPUT
INPUTS
OUTPUT
FC
A
B
A
FC
A
B
A
0
0
1
0
128
0
1
1
0
1
1
1
128
1
1
0
0
0
0
0
128
0
0
1
0
1
0
1
128
1
0
0
FC
A
B
A OR B
FC
A
B
A OR B
1
0
1
1
129
0
1
0
1
1
1
1
129
1
1
0
1
0
0
0
129
0
0
1
1
1
0
1
129
1
0
0
FC
A
B
A AND B
FC
A
B
A AND B
2
0
1
0
130
0
1
1
2
1
1
1
130
1
1
0
2
0
0
0
130
0
0
1
2
1
0
0
130
1
0
1
FC
A
B
A XOR B
FC
A
B
A XOR B
3
0
1
1
131
0
1
0
3
1
1
0
131
1
1
1
3
0
0
0
131
0
0
1
3
1
0
1
131
1
0
0
FC
A
B
A OR NOT B
FC
A
B
A OR NOT B
4
0
1
0
132
0
1
1
4
1
1
1
132
1
1
0
4
0
0
1
132
0
0
0
4
1
0
1
132
1
0
0
FC
A
B
A AND NOT B
FC
A
B
A AND NOT B
5
0
1
0
133
0
1
1
5
1
1
0
133
1
1
1
5
0
0
0
133
0
0
1
5
1
0
1
133
1
0
0
FC
A
B
J–K LATCH
FC
A
B
J–K LATCH
6
0
1
0
134
0
1
1
6
1
1
opposite last value
134
1
1
opposite last value
6
0
0
unchanged
134
0
0
unchanged
6
1
0
1
134
1
0
0
FC
A
B
D LATCH
FC
A
B
D LATCH
7
0
1
0
135
0
1
1
7
1
1
1
135
1
1
0
7
0
0
unchanged
135
0
0
unchanged
7
1
0
unchanged
135
1
0
unchanged
Unchanged means the value from the last execution is used.
Opposite last value means the opposite of the value from the last
execution is used.
FCS 53MC5000 Flexible Control Strategies
2-16
LOGC-AB