Continuous Control Functions

PID CONTROL BLOCK

2-27

67

Control Mode (CMS) ..........................................................................................................CWR
This is the active controller mode. The controller mode can be represented as a separate
output and setpoint mode, or singly as a controller mode. If controller mode is used, the
following conditions are checked:

•

A remote setpoint source must be configured

•

Allowed output modes and allowed setpoint are set to M.A and L.R by the configurator

•

Setpoint and output modes, restart modes and allowed modes may not be entered by the
user

•

Setpoint and output modes and restart modes take on values based on the user entered
value for controller mode/restart mode. These values are:

Controller Mode

Output Mode

Setpoint Mode

CASCADE

AUTO

REMOTE

AUTO

AUTO

LOCAL

MANUAL

MANUAL

Don’t Care

TRACK

TRACK

Don’t Care

The control mode states are:

MANUAL

0

The active control mode is manual.

AUTO

1

The active control mode is auto.

CASCADE

2

The active control mode is cascade.

TRACK

3

The active control mode is track (track input signal is asserted and
track value is copied to the output).

FAULT

5

A FAULT mode is entered when the block mode cannot be
determined (e.g., when track command input quality is bad), and can
only be cleared by an operator command.

N/A

15

Configurator entry when setting mode model to SP/OP MODE only.

68

Control Mode Status Quality (CMSQ)............................................................................. – WR
Control mode status quality is determined by the block state and the mode model.

GOOD

0

Quality when the block is RUN or HOLD and the mode model is
control mode.

BAD

1

Quality when the block is OFF or the mode model is setpoint/output
mode.

69

Control Mode Command (CMC) .......................................................................................– – R
The control mode command is the mode to which the controller returns after leaving TRACK.
If you are in Track and want to return to a control mode other than the value indicated here,
you must write to the Controller Mode (CMS) whose value will then be reflected here.

MANUAL

0

Controller returns to MANUAL after leaving TRACK.

AUTO

1

Controller returns to AUTO after leaving TRACK.

CASCADE

2

Controller returns to CASCADE after leaving TRACK.

Advertising