Application Examples
A connection is then made from input STOP in each of the Display Blocks to an Expression
block that controls the scrolling, as shown in the next figure.
Block connections,
auto scrolling
displays
In this example the Expression Block uses inputs 1 through 3, configured as Count inputs, to
detect the “stop scroll” command from the Display Blocks named TAG1, TAG2 and TAG3.
“DISPLAYS” is a count input with an initial value of 1, that increments the display index
number by 1 until it reaches 3, then resets to 1 and starts again, as long as none of the “stop
scroll” inputs is present. The result of the Expression must be connected back around to the
input DISPLAYS.
Expression Block
Inputs
The expression for the Expression Block is:
Expression to
control scrolling
IF (TAG1 == 0 || TAG2 == 0 || TAG3 == 0) THEN
DISPLAYS
ELSE IF DISPLAYS =< 2 THEN
DISPLAYS + 1
ELSE 1