MODBUS RTU

COMMUNICATIONS GUIDE

21

Table 12. MODBUS Reference Information for MOD30 ML and Modcell Communications

Code

Function

Action

Data Types

Max Points per

Command

Address

Range

From

To

01

Read Coil Status

Read one or more
consecutive points

Discrete

99

00001-00499

CL

DRWIN1-5

02

Read Input Status

Read one or more
consecutive points

Discrete

99

10001-10499

CL

DROIN1-5

03

Read Holding
Registers

Read one or more
consecutive registers

All except ASCII and HEX -
One Register per Point

32

40001-40499

ML

SRWIN1-5

Any - Uses as many
Registers as req'd for Data

125

41001-45999

CL

MRWIN1-5

04

Read Input
Registers

Read one or more
consecutive registers

All except ASCII and HEX -
One Register per Point

32

30001-30499

ML

SROIN1-5

Any - Uses as many
Registers as req'd for Data

125

31001-35999

CL

MROIN1-5

05

Force Single Coil

Write one point

Discrete

1

00001-00499

CL

DRWIN1-5

06

Preset Single
Register

Write one register

All except ASCII and HEX -
One Register per Point

1

40001-40499

ML

SRWIN1-5

Any - Uses as many
Registers as req'd for Data

1

41001-45999

CL

MRWIN1-5

08

Loopback Test

Return of Query (00)

For Diagnostic Use Only

N/A

N/A

N/A

N/A

15

Force Multiple
Coils

Write one or more
consecutive points

Discrete

16

00001-00499

CL

DRWIN1-5

16

Preset Multiple
Registers

Write one or more
consecutive registers

All except ASCII and HEX -
One Register per Point

16

40001-40499

ML

SRWIN1-5

Any - Uses as many
Registers as req'd for Data

16

41001-45999

CL

MRWIN1-5

65

Extended Modbus Read and/or Write any

Data Type

Any - Data in buffer, rather
than Coils or Registers

Note 6

n/a

CL

FGLISTIN

NOTES:

1. Placing discrete points into Holding or Input Registers uses an entire 16 bit register for one point. This

may be more efficient when only a small amount of discrete data is required, along with analog data. If a
significant number of discrete points are required, communications and memory efficiency would be
improved by placing them into the Coil or Input Status area. Another possibility would be to pack 16
discrete points into a count and store it in an Input or Holding Register. This would be dependent on the
host device's ability to accept the packed data format.

2. Date, Floating Point and mSec Time are converted to 16 bit integers when tied to an ML register.

3. It is recommended that no more than the number of points supported per command be put into each Slave

ML block. This will prevent the Master device from accessing more than the allowed number of points in a
single command. The instrument will not return any data if the maximum number of registers is exceeded
or an invalid register is included. Some HMI packages, such as Fix DMACS, allow poll records to be
broken into groups to avoid this problem.

4. When using Extended Modbus, group control loop data together in CL blocks for greatest efficiency.

5. Some peripheral equipment that is designed for Modbus communications may not support Extended

Modbus (function code 65).

6. The instrument's foreground can hold up to 2400 bytes of data. The number of points that can be handled

per command depends on the host software. Connecting the CL block to BGLISTIN may provide
increased performance with some host configurations. This is the case when using Database Caching
with PC-30 or Genesis for Windows. Without Database Caching enabled, a connection to FGLISTIN is
recommended.

7. Each Modbus List block can contain up to 99 points, and each type of connection provides inputs for five

lists. This is also true for Configured List blocks for Standard Modbus. When using Extended Modbus,
Configured List blocks may be nested, allowing more than 99 points to be connected to FGLISTIN or
BGLISTIN.