Radiant tube assembly – Detroit Radiant Products Company DES3 Series User Manual
Page 16
 
16
Radiant Tube Assembly
To install the radiant tubes:
Place tubes in hangers with the welded seam facing downward and the swaged end of the tube 
towards the exhaust end of the heater system (see figure 3.8).
Refer to the Series Insert Manual for tube installation sequence. Place the combustion chamber as 
the first tube connected to the burner control box. These tubes have an identification sticker on the 
swaged end.
Slide tube clamps onto radiant tubes (see figure 3.9).
Figure 3.8
•
Attach Hangers
Figure 3.9
•
Attach Tube Clamps
Hanger
Welded Seam
Faces Down
Swaged End
Tube Clamp
Radiant Tube
3.0
Installation
•
Radiant Tube Assembly
IMPORTANT! 150,000 to 200,000 BTU/h models must be 
installed with a stainless steel tube clamp (P/N: TP-220) located at 
the seam between the primary combustion chamber and the 
second tube section downstream of the burner control box.
NOTE: If the tube clamp comes 
apart, the spacer 
must be
re-assembled with the spacer’s 
concave surface facing against 
the radiant tube surface.
Concave surface
1
2