Maintenance

Troubleshooting Guide

Check to make sure gas pressure is

within minimum and maximum inputs, as

indicated on the heater’s rating plate.

Is the gas pressure OK?

Is the heater properly

grounded? Is the heater’s

polarity correct?

Replace gas valve.

Correct problem.

No

Correct problem.

No

On the outside of the control box, is there

24V across the ‘W2’ and ‘C’ connectors on

the terminal strip?

Repair or replace faulty

wiring or thermostat.

Replace relay board.

No

If heater does not go into high fire mode:

Measure voltage across the ‘HI’ and

the ‘C’ connectors on the gas valve.

Is it 24V?

Yes

No

Yes

Replace gas valve.

NOTE: To confirm that the heater is not in high fire mode, check manifold pressure.

If manifold pressure is 3.3” to 3.5” for natural gas or 9” to 10” for propane, the light is faulty and should

be replaced.

When the heater is in low fire mode, manifold pressure is approximately 2.0” to 2.5” for natural gas or

5.0” to 6.5” for propane. If this is the case, the following troubleshooting steps should be followed:

Yes

Replace the appropriate pressure switch

after verifying:

• There is continuity across the thermal fuse.

• Heater, fan blowers ,squirrel cage, intake

and exhaust are clean and free from dirt and

obstructions.

• The 4” air intake pipe does not exceed 20 ft.

and/or 2 elbows.

• There is not a negative pressure experienced

at the area of air intake (e.g.; high winds, attic

space, tightly sealed building).

Continued from page 51

The heater is equipped with two safety

pressure switches. The burner switch is a

normally open switch and the exhaust switch

is a normally closed switch.

Temporarily

place jumpers across the terminals of the

exhaust switch (reinstall control box cover).

Does the igniter glow red?

NOTE: If normal operation does not continue

after bypassing the exhaust switch, consult

factory to troubleshoot the burner switch prior

to continuing.

Yes

No

With a microampmeter, check

DC amperage at flame rod. Is it

greater than .07 microamps?

Check to make

sure flame sensor

wire is OK and

then replace

circuit board.

Sensing rod is faulty or

flame is weak. Check

to make sure heater is

operating at proper gas

pressure as indicated on

heater’s rating plate and

then, if needed, replace

sensing rod.

Yes

Yes

No

Replace circuit

board.