FUNCTION CODE

LOCAL PROGRAMMING

27

RS-232 or MODEM

(Default setting is 1 for MODEM)

You may program the system via

built-in RS-232 (local) or MODEM

(remote)

1= MODEM

0= RS-232

28

DIRECTORY DIGIT

(Default setting is 3-Digit)

The number of digit on the tenant

code (directory code) must be set

before the tenant database is

programmed on Function Code 20

and Function Code 30.

29

ALARM DELAY

(Default setting is 15 seconds)

• Report ALARM (00-90 seconds) if

Door 1 or DOOR 2 is open longer

than the Door Open Interval set on

Function Code 02 (door sensor

switch must be installed)

• Report ALARM (00-90 seconds) if

DOOR 1 or DOOR 2 is forced open

(door sensor switch must be

installed).

• Trigger relay 2 if set for MODE 2 (A

SHUNT) (00-90 seconds).

Step 1

Log on to programming mode (see section 3.1). The display shows

Step 2

Enter Function Code 27 then press # and the display shows

Step 3

Enter 0=RS-232 then press # and proceed to step 5 or 1=MODEM then
press #, the display shows

Step 4

Enter 1 or 0 then press #, the display shows

Step 5

Select another Function Code to program different field from the table or
press * to exit the programming mode.

Step 1

Log on to programming mode (see section 3.1). The display shows

Step 2

Enter Function Code 28 then press # and the display shows

Step 3

Enter the directory digit (2, 3 or 4 digit) then press # the display shows

then the display shows

Step 4

Select another Function Code to program different field from the table or
press * to exit the programming mode.

Step 1

Log on to programming mode (see section 3.1). The display shows

Step 2

Enter Function Code 29 then press # and the display shows

Step 3

Enter 00 - 90 then press #, the display shows

Step 4

Select another Function Code to program different field from the table or
press * to exit the programming mode.

Pach and Company

Chapter 3

Page 23

AeGIS NPB9000P Series

PROGRAMMING

06/20/11

SELECT PROGRAM
ENTER: _ _ PRESS #

Rs232/Modem
0=232, 1=Modem: 1

Protocol: 1_V22
0=Bell212 :1

SELECT PROGRAM
ENTER: _ _ PRESS #

DIR DIGITS
ENTER: 3 PRESS #

% SORTING DATA %
Please Wait . . .

SELECT PROGRAM
ENTER: _ _ PRESS #

SELECT PROGRAM
ENTER: _ _ PRESS #

ALM DELAY: 00 - 90
ENTER: 1 5 PRESS #

SELECT PROGRAM
ENTER: _ _ PRESS #

SELECT PROGRAM
ENTER: _ _ PRESS #