5. HOW TO REMOVE SMOKE ALARM FROM BASE PLATE

5.1 Look for ‘SLIDE TO REMOVE’.
5.2 Remove Tamper Locking Screw if installed.

5.3 Push firmly towards arrow until smoke alarm unhinges from base plate.

5.4 To re-install smoke alarm follow FIGURE 2 procedure 1 to 3. See page 9.

6. INSTALLATION

WARNING: THIS SMOKE ALARM MUST BE INSTALLED BY QUALIFIED

(LICENSED) ELECTRICIANS ONLY.

6.1

Wiring Instructions

:

6.1.1 In the interests of safety, this smoke alarm and all wiring must be installed by

a licensed electrician in accordance with the relevant requirements of the
SAA Wiring Rules - AS3000.

6.1.2 DO NOT connect this smoke alarm on the base plate without the presence of

240V mains power.

6.1.3 This Smoke Alarm can only interconnect with LIFESAVER Model 5000,

5800, 5800RL, 3000, 4800RL Smoke Alarms; Heat Alarm model HA240
and visual Signaling Device model SL240 and isolation relay model
RK10A/9. Interconnection with other brands may cause damage or result in a
shock or fire risk and void warranty.

6.1.4 Due to “noise” from electromagnetic interference, up to 24 units of smoke

alarms and compatible products may be interconnected.