Operation, Central heat operation - firing rate screen – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual

Page 42

Advertising
background image

© The Fulton Companies 2014

3-8

OPERATION

EDR-IOM-2014-0318

SECTION 3

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.

for maintenance and/or commissioning purposes (to be able to run the
boiler anywhere in the fi ring range) you would press the yellow block next
to Firing Rate. Pressing Firing Rate will put you into the screen shown in
Figure 14. When the Setpoint or Firing Rate requires changing, a password
is required. Once the password is entered correctly, the top right section
of the screen will show the padlock unlocked as shown in Figure 13. See
Figures 14 and 15 for changing the Setpoint and Firing Rate.

NOTE:

If the boiler is not placed back in automatic mode following

maintenance, the boiler will not operate properly.

Central Heat Operation - Firing Rate Screen

In this screen (Figure 14) the control can be changed from Automatic to Manual.
When in Automatic, the control will go to the fi ring rate necessary to achieve the
setpoint. When in Manual, the control will go to the point that is entered into
the Manual Firing Rate box; specifi c RPMs can be entered. After a fi ring rate is
entered, press OK and the Firing Rate Screen will close and the boiler will go that
selected fi ring rate. When fi nished with maintenance, return to this screen and
place the boiler back into Automatic mode.

FIGURE 13 - CENTRAL HEAT OPERATION SCREEN

FIGURE 14 - CENTRAL HEAT OPERATION - FIRING RATE SCREEN