Operation, Changing high limit setpoint and verifying change – Fulton Endura (EDR) Condensing Hydronic Boiler User Manual
Page 44

© The Fulton Companies 2014
3-10
OPERATION
EDR-IOM-2014-0318
SECTION 3
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.
the previous Setpoint screen to the Modulation Screen (Figure 17). This screen
provides access to the PID (Proportional, Integral and Derivative) of the control.
The sola password is also required to change these parameters.
Changing High Limit Setpoint and Verifying Change
From the Status Summary Screen press Confi gure, then High Limits; this screen
will be used to set and/or test the Outlet High Limit Setpoint (Figure 18). The
sola password must be entered. By touching the Setpoint next to Outlet High
Limit Setpoint you can adjust the temperature up and down for the Setpoint you
desire or lower it for testing purposes. This change will require Verifi cation. Verify
as follows:
1. Arrow back to the Confi guration Menu and press Verify down in the lower
right hand corner. Figure 19.
FIGURE 17 - CENTRAL HEAT CONFIGURATION - MODULATION SCREEN
FIGURE 18 - HIGH LIMITS SCREEN