Air source models, Applications, Performance – Fulton Invictus (IVS) Heat Pump Systems User Manual

Page 4: Thermal efficiency vs. outdoor air temperature

Advertising
background image

ELECTRIC

CHILLER

(Off)

HEAT PUMP

BOILER

HEAT

LOAD

O

utside W

all

OUTDOORS

INDOORS

SYSTEM

PUMP

ELECTRIC

CHILLER

COOLING

LOAD

O

utside W

all

OUTDOORS

INDOORS

(Off)

HEAT PUMP

BOILER

SYSTEM

PUMP

AIR SOURCE MODELS

APPLICATIONS:

The air source models of the gas

absorption heat pump can be used

for hydronic heating and cooling

applications. The IVS-095-A model is

for heating only, and the IVS-095-AR

is heating/cooling reversible.

Hydronic Cooling Capacities:

(IVS-095-AR Model)

Hydronic Heating Efficiencies:

(IVS-095-A Model)

PERFORMANCE:

75

70

65

60

55

50

45

40

35

30

25

20

15

10

5

0

-5

-10 -15 -20

150
145
140
135
130
125
120

115
110

105
100

95
90
85

Ambient Temperature (°F)

Th

er

m

al

E

ffic

ie

nc

y,

P

er

ce

nt

Heating

Setpoint:

86°F

113°F

122°F
140°F

Thermal Efficiency vs. Outdoor Air Temperature

Outdoor Temp.

(°f)

Output (bTu/hr, Tons)

37.4°f setpoint

Output (bTu/hr, Tons)

44.6°f setpoint

Output (bTu/hr, Tons)

50.0°f setpoint

59

64,800

5.40

63,800

5.32

64,800

5.4

66

63,500

5.29

63,500

5.29

64,100

5.34

77

60,100

5.01

62,400

5.20

63,300

5.28

86

54,300

4.53

60,700

5.06

61,800

5.15

95

44,000

3.67

57,700

4.81

59,400

4.95

104

.....

.....

51,200

4.27

54,600

4.55

113

.....

.....

.....

.....

46,100

3.84

Graphic: Air source models are installed

outdoors.