SPECIFICATIONS

AND DIMENSIONS

specifications:

EnERgy sOuRcE

aIR sOuRcE

WaTER / gROunD sOuRcE

mODEl

IVs-095-a IVs-095-aR

IVs-095-W IVs-095-Wlb

Dimensions:

Width IN

33.5 33.5 33.5 33.5

Length

IN 48.5

48.5

25.75

25.75

Height IN

50.75 50.75 50.75 50.75

Application

Heating Only

Heat / Cool Reversible

Heat / Cool Simultaneous Heat / Cool Simultaneous

Environmental Component

Outdoor Air

Outdoor Air

Water (Lake / Pond)

Ground

Input

BTU/Hr

95,500 95,500 95,500 95,500

Max Output Heat

BTU/Hr

139,200

134,800

142,600

133,800

Max

Efficiency

%

146 141 149 140

Max Output Cool BTU/Hr (Tons)

N/A

64,800 (5.4)

59,400 (4.9)

58,400 (4.9)

Max

Hot

Water

Temp

°F

140 140 149 140

Min Cold Water Temp

°F

37

37

37

37

Max Ambient Op. Temp

°F

113

113

113

113

Min Ambient Op. Temp

°F

-20

-20

10

10

Electrical

Rating

V/Ph/Hz

208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60

Electrical Consumption

kW

0.75

0.75

0.4

0.4

Advertising