Specifications – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Steam) Oil Fired User Manual

Page 14

Advertising
background image

ffsstd-pds-2011-1222

Specifications

Models ICS/ICX/FB

4

6

9.5

10

15

20

25

30

50

60

Boiler Connections

N. Steam Outlet 15 PSI

1”

1”

N/A

1.5”

2”

3”

3”

3”

4”

4”

25

NPT

NPT

NPT

CL150# CL150# CL150# CL150#

CL150#

Flange

Flange

Flange Flange

Flange

N. Steam Outlet 150 PSI

0.75”

0.75”

1”

1”

1.25”

1.5”

2”

2”

3”

3”

19

NPT

NPT

NPT

NPT

NPT

NPT

NPT CL150#

CL150#

Flange

Flange

O. Safety Valve Outlet 15 PSI

IN

0.75

0.75

N/A

0.75

1

1.5

1.5

1.5

2

2

MM

19

19

19

32

38

38

38

38

38

O. Safety Valve Outlet 150 PSI+

IN

1

1

1

1

1

1

1

1

1.25

1.25

(9.5 HP 100 PSI)

MM

25

25

25

25

25

25

25

25

32

32

P. Safety Valve Inlet 15 PSI++

IN

0.75

0.75

N/A

0.75

1

1.25

1.25

1.25

1.5

2

MM

19

19

19

25

32

32

32

32

32

P. Safety Valve Inlet 150 PSI

IN

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

1

1

(9.5 HP 100 PSI)

MM

19

19

19

19

19

19

19

19

25

25

Q. Feedwater Inlet

IN

0.75

0.75

1

1

1

1

1

1

1

1

MM

19

19

25

25

25

25

25

25

25

25

R. Blowdown Outlet

IN

1

1

1

1

1

1.25

1.25

1.25

1.5

1.5

MM

25

25

25

25

25

32

32

32

38

38

S. Water Column Blowdown

IN

1

1

1

1

1

1

1

1

1

1

MM

25

25

25

25

25

25

25

25

25

25

Ratings* (Sea level to 3000 ft.)
Output

1000 BTU/HR

134.40

201

318

335

503

670

838

1005

1674

2009

1000 KCAL/HR

33.8

50.7

80.1

84.4

127

169

211

253

422

506

Steam Output

LB/HR

138

207

328

345

518

690

863

1035

1725

2070

KG/HR

63

94

149

157

235

313

392

470

785

942

Approximate Fuel Consumption at Rated Capacity+++
Light Oil

GPH

1.2

1.8

2.8

3.0

4.5

6.0

7.5

9.0

15.0

17.9

LPH

4.5

6.8

10.6

11.4

17

22.7

28.4

34.1

56.8

67.8

Propane Gas (ICS)

FT3/HR

67.2

100

159

168

251

335

419

502

837

1004

(14” w.c. req’d)

M3/HR

1.9

2.8

4.5

4.8

7.1

9.5

11.9

14.2

23.7

28.4

Propane Gas (ICX)

FT3/HR

63

97

161

242

323

404

484

(14” w.c. req’d)

M3/HR

2.2

2.7

N/A

4.6

6.9

9.1

11.4

13.7

Natural Gas (ICS)

FT3/HR

168

257

398

419

628

837

1047

1256

2093

2511

(7” - 11” w.c. req’d)

M3/HR

4.8

7.1

11.3

11.9

17.8

23.7

29.7

35.4

59.3

71.1

Natural Gas (ICX)

FT3/HR

159

242

384

403

606

807

1009

1210

(7” - 11” w.c. req’d)

M3/HR

5.6

6.9

10.8

11.4

17.2

22.9

28.6

34.3

Natural Gas Boiler

IN

1

1

1

1

1

1.25

1.25

1.5

1.5

2

Connection Size (Std CSD-1)

MM

25

25

25

25

25

32

32

38

38

51

Oil Inlet Size

IN

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

1/4

MM

6

6

6

6

6

6

6

6

6

6

Burner

3450 RPM/60 CY

1/3 gas

1/3 gas

1.5 gas 1.5 gas

Motor HP

2850 RPM/50 CY

1/3

1/3

1/3

1/3

1/3

3/4 oil

3/4 oil

3/4

2 oil

2 oil

Electric Power Requirements - Burner Only (in Amps) ***
120V,60 CY, 1 Phase

5.2

5.2

5.2

5.2

5.2

5.2 gas

5.2 gas

9.2

--

--

9.2 oil

9.2 oil

240V, 50/60 CY, 1 Phase

2.6

2.6

2.6

2.6

2.6

2.6 gas

2.6 gas

4.6

8.9 gas 8.9 gas

4.6 oil

4.6 oil

9.5 oil

9.5 oil

208V, 50/60 CY, 3 Phase

1.9

1.9

1.9

1.9

1.9

1.9 gas

1.9 gas

3.1

4.4 gas 4.4 gas

3.1 oil

3.1 oil

5.7 oil

57 oil

240V, 50/60 CY, 3 Phase

1.6

1.6

1.6

1.6

1.6

1.6 gas

1.6 gas

2.8

4.2 gas 4.2 gas

2.8 oil

2.8 oil

5.4 oil

5.4 oil

480V, 50/60 CY, 3 Phase

0.8

0.8

0.8

0.8

0.8

0.8 gas

0.8 gas

1.4

2.1 gas 2.1 gas

1

.4 oil

1.4 oil

2.7 oil

2.7 oil

Water Content

U.S. GAL

14

16

16

24

39

77

82

170

245

270

LITERS

53

61

61

91

148

292

310

644

927

1022

Specifications and Dimensions are approximate. We reserve the right to change specifications and/or dimensions..+ High pressure boilers purchased with low pressure
openings may have larger than specified opening sizes, consult factory for correct opening sizes.++ 50 and 60 HP have two safety valves on low pressure.
+++Consumption based on light Oil 140,000 BTU/G; Natural Gas 1000 BTU/ft.

3

; Propane 2500 BTU/ft

3

. *All ratings from 0 PSIG and at 212 degrees F. *** Control

circuit electrical requirement will vary with the system voltage, please consult factory. --Consult factory.

The Fulton Companies
972 Centerville Road
Pulaski, NY 13142
Call 315-298-5121
Fax 315-298-6390
www.fulton.com

6b-O 4/00