6-8 Communications

CMD

(hex)

Name

Function

1E

Grp Offset

Output group offset value.

Put:

! ADR 1E P XX YYYY CSM <CR>

Reply:

A <CR>

Get:

ADR 1E G XX CSM <CR>

Reply:

A YYYY CSM <CR>

where “XX” is the group number minus 1. “YYYY” is the offset
value for that group, in hex.

3C

Shaft Offset

Shaft position offset.

Put:

! ADR 3C P XXXX CSM <CR>

Reply:

A <CR>

Get:

! ADR 3C G CSM <CR>

Reply:

A XXXX CSM <CR>

where “XXXX” is the shaft offset in hex.

1F

Grp Chn Qty

Number of channels in a specified output group.

Put:

! ADR 1F P XX YY CSM <CR>

Reply:

A <CR>

Get:

! ADR 1F G XX CSM <CR>

Reply:

A YY CSM <CR>

where “XX” is the group number minus one. “YY” is the number
of output channels in that group, in hex.

21

Mode

Mode for the specified output group.

Put:

! ADR 21 P XX YY CSM <CR>

Reply:

A <CR>

Get:

! ADR 21 G XX CSM <CR>

Reply:

A YY CSM <CR>

where “XX” is the group number minus one. “YY” is the operating
mode, from zero to five.

47

Output Enab

Output Enable ANDing on or off for specified channel.

Put:

! ADR 47 P XX <00 or 01> CSM <CR>

Reply:

A <CR>

Get:

! ADR 47 G XX CSM <CR>

Reply:

A <00 or 01> CSM <CR>

where “XX” is the channel number minus one, in hex. “00” =
ANDing “off”; “01” = ANDing “on”.

4D

Pgm Sel Mode

Program select terminals use Binary, Gray Code, or BCD format.

Put:

! ADR 47 P <00, 01, or 02> CSM <CR>

Reply:

A <CR>

Get:

! ADR 47 G CSM <CR>

Reply:

A <00, 01, or 02> CSM <CR>

“00” = Binary; “01” = Gray Code; “02” = BCD.

Serial Commands (cont’d)

Configuration
Commands
(cont’d)