8.3

Replacements

WARNING:

DO NOT CONNECT OR DISCONNECT CABLES OR OTHER SYSTEM

COMPONENTS WITH POWER APPLIED. FOLLOW LOCKOUT/TAGOUT AND
OTHER APPLICABLE SAFETY PRECAUTIONS WHEN CONNECTING OR

DISCONNECTING CABLING, WIRING, AND EQUIPMENT.

NOTE: When replacing the AFC1100 System Axis unit, ensure that the new unit is

configured with the same hardware and software as the unit being replaced.

8.3.1 Axis Unit Replacement (No Partial Replacement - Complete Unit Only)

When one Axis unit is being replaced with another, it is important to verify that both Units are
the same Type. (Refer to Section 2.4 Axis unit and to the chart, below.)

Note:

Although "A" type Axis units (AXIS-103A, for example) accomodate the same nutrunners as
their older style counterparts, they are not fully interchangeable. REPLACE OLDER STYLE
AXIS UNITS WITH THE SAME, AND REPLACE THE "A" TYPE UNITS WITH OTHER "A"
TYPE UNITS. If it is necessary to intermix older style Units with "A" type Units, contact FEC
INC. for guidance.

AXIS-110 / 105

DFT-502M4-S/O

AXIS-105 / 105

DFT-302M3-S/O

AXIS-105 / 105

DFT-202M3-S/O

AXIS-105 / 105

DFT-152M3-S/O

AXIS-105 / 105

DFT-132M3-S/O

AXIS-105 / 105

DFT-801M3-S/O

AXIS-105 / 105

DFT-601M3-S/O

AXIS-103 / 103

DFT-401M2-S/O

AXIS-103 / 103

DFT-401M1-S/O

AXIS-103 / 103

DFT-201M1-S/O

AXIS-103 / 103

DFT-101M1-S1/O1

AXIS UNIT

TOOL TYPE

1. Verify the enclosure power is off. Ensure all cables connected to the front of the Axis unit

are clearly marked (for reconnection).

2. Disconnect all cables from the front of the unit.

3. Loosen (do not remove) the four (4) screws that secure the Axis unit to the back panel.

The upper bracket of the Axis unit has two slotted holes, and the bottom bracket has two
open-ended slots.

4. Lift up and out on the Axis unit to remove.

5. Verify the Axis unit dip switches are set to the appropriate spindle number and ramp-up

time. Refer to Section ?.

6. Verify the Axis Units have the same configuration (hardware and software).

7. Install the new Axis unit in reverse order of removal.

8. Apply power to the enclosure. After approximately 30 seconds, the System will finalize the

Power On Self Test (POST).

9. The Axis unit will require reentry of the preset data. Refer to Chapters 6 and 7.

Chapter 8: Maintenance and Inspection (Rev. 8/98)

Page 8-7