APPENDIX K: ERROR CODES (Continued)

Error

Name

Description

Explanation and/or Possible Causes

Pressure

Pot Empty

Inlet

Pressure

Loss

Outlet

Pressure

Loss

Analog

Remote

Loss

Ratio

Out of

Tolerance

Motor

Amplifier

Fault

Analog

Feather

Loss

Analog

Spare

Loss

Foldback

Pressure

Reached

The system has determined the

pressure pot is empty for the

respective channel

The electrical current from the

Pump Inlet

Pressure Sensor is less than 1

milliamp

The electrical current from the

Pump Outlet Pressure sensor is

less than 1 milliamp

The electrical current from the

Remote Analog Setpoint source

is less than 1 milliamp

The difference between the de-

sired ratio and the actual ratio,

expressed as a percentage error,

exceeds the Flow Rate/Ratio Tol-

erance Percentage value speci-

fied in the Gun Configuration.

The motor amplifier has detected

a fault condition.

The electrical current from the

Feather pressure sensor is less

than 1 milliamp

The electrical current from the

Spare Analog Input sensor is

less than 1 milliamp

The Pump Outlet pressure has

exceeded the Foldback Pressure

value specified in the System

Configuration

1. The value entered for the pressure pot

Capacity in the Job Configuration is

Incorrect.

2. The operator neglected to reset the

Pressure Pot.

Capacity when it was last filled.

3. Pressure Pot is empty.

1. Electrical connection problems.

2. Failure of Pump Inlet Pressure sensor.

1. Electrical connection problems.

2. Failure of Pump Outlet Pressure sensor.

1. Electrical connection problems.

2. The Remote Analog Setpoint source is

configured for voltage instead of current

loop.

1. Loss of feedback signal from motor

amplifier or flow meter.

2. Incorrect Calibration Factor in Channel

Configuration.

3. One or both channel is unable to deliver the

correct flow rate due to restriction in the

fluid line, lack of material.

1. Reference the motor amplifier diagnostics

to determine the cause of the fault.

1. Electrical connection problems.

2. Failure of Feather Pressure sensor.

1. Electrical connection problems.

2. Failure of Spare Analog input sensor.

1. This error is normal when operating in Fast

Fill or Channel Fill mode.

2. For Automatic guns, restriction in the fluid

line.

3. For Automatic guns, failure of applicator

trigger valve.

Source

Channel

Card

Channel

Card

Channel

Card

Channel

Card

Channel

Card

Channel

Card

Channel

Card

Channel

Card

Channel

Card