Drain Connection

During defrost cycle the HRV unit may produce some condensation and the water should flow into a nearby drain.

The HRV cabinet has pre-punched holes(two on side and one on the door) for the drain, in order to keep the drain pan
intact,

hand tighten the plastic drain spout to the unit using the gasket and nuts.

Cut two sections of ½" drain pipe and connect the other ends to the drain spout then connect to “T” connector. Connect a
drain line and create a

P-trap to prevent the unit from unpleasant odours from drain source. Tape or fasten base to avoid

any bends.

The HRV and all condensate lines must be installed in a space where the temperature

is maintained above the freezing point or freeze protection must be provided.

CAUTION

!

!

Note:
For Horizontal installation,
connect only 1 drain spout assembly on lid / door.
cut one ½’’ drain pipe and connect one end to the drain spout and the other
end to the drain line. Don't forget to create a P-trap as shown above.

“ T ” Connector

½” I.D.

Drain Pipe

Zip Tie

Drain Spout

to Drain

Drain Pan

“P” Trap

Drain Pan

For Vertical installation

Drain Spout Assembly

Rubber washer

Drain Spout

Nut

Steel washer

HRV/ERV Steel Housing

Plastic Drain Pan

Minimum 5 Feet

(1” Thick)

Intake

Exhaust

Insulation

CAULKING GRILLE

- 3 SIDES ONLY, NOT ON BOTTOM

CAULKING WALLBOX

- CAULK WALLBOX TO
STRUCTURE ON ALL 4 SIDES

Distance

“X”

“Single Vents Only”

Metal Clamp

Insulation

Duct

Backdraft
Damper

Grille

Insulation

Wallbox

Access Door


-
Fresh air intake and supply duct must be totally insulated. Exhaust duct
must be 5 feet insulated from the wall. In colder climate, it is recommended
to insulate all exhaust and supply ducts.

Note:

HRV and ERV Typical Installations (cont’d)

10

-Use appropriate access door size and install on proper
location for easy access to all HRV/ERV components for
routine check and maintenance of the unit.
For more info visit
http://www.reversomatic.com/HRV&ERV/Accessories

Lid

Typical Installations of Single Vents & Access door

(For vertical installation)

Use this drain for
horizontal installation

*Re - Circulation Efficiency
If distance “X” is 5ft - 99.7%