Robinair 22791 Infrared Refrigerant Leak Detector User Manual

Page 5

Advertising
background image

Mute Button
Press the MUTE button to toggle the audio portion of No. 22791

ON or OFF.
Peak Button
The PEAK function stores the highest change in refrigerant

concentration achieved while continuing to detect leaks. Press

the PEAK button to toggle this function ON and OFF. The PEAK

LED illuminates when this function is turned on. Turning the PEAK

function off clears the peak information.
Contaminate Mode
To detect even the smallest leak in refrigerant-contaminated

environments, press the PEAK button rapidly four times. The

green LED will flash rapidly to show contamination mode is

on. Press the PEAK button rapidly four times again to turn

contamination mode off.

Leak Detection Procedure

1. Press and hold the ON/OFF button for one second. The warm-

up and calibration sequence takes approximately 30 seconds.

The sensitivity level defaults to HIGH at startup.

2. The most likely place for a refrigerant leak is at soldered joints

in refrigerant lines and changes in cross section or direction

of these lines. No. 22791 detects changes in concentration

of refrigerant, not the absolute concentration of refrigerant.

This allows the detection of leaks in locations that may have

refrigerant in the air. Use the following “double pass” method

to find leaks from the detection of change in refrigerant

concentration. Leak test with the engine off.

A. Charge the system with sufficient refrigerant to have a

gauge pressure of at least 340 kPa (50 psi) with the system

off. At ambient temperatures below 15°C, leaks may not be

measurable because the pressure may not be reached.

B. Visually trace the entire refrigerant system, and look for

signs of air conditioning lubricant leakage, damage, and

corrosion on all lines, hoses, and components. Check

each questionable area with the detector probe, as well

as all fittings, hose-to-line couplings, refrigerant controls,