service valves with caps in place, brazed or welded areas,

and areas around attachment points and hold-downs on

lines and components. If looking for an apparently larger

leak, check first at the 7 g/yr or 14 g/yr position.

C. Always follow the refrigerant system around in a continu-

ous path so no areas of potential leaks are missed. If a

leak is found, continue to test the remainder of the system.

D. Recheck service valves with caps removed. Blow shop air

over service valve to clear immediate area, and then check

with detector on 7 g/yr setting.

E. Move the detector at a rate of no more than 75 mm/sec

(3 in/sec) and as close as possible to 9.5 mm (3/8 in)

from the surface, completely encircling each test position

(switch, sensor, refrigerant tubing connection, etc).

F. Slower movement and closer approach of the probe

normally improve the likelihood of finding a leak. However,

detectors made to meet this standard are based on air

sampling from the 9.5 mm (3/8 in) distance. Retest is

advisable when a leak appears to be found at the most

sensitive settings, particularly if the probe was in a static

position on a joint, or making physical contact with a joint,

as it was moving. Repeat with a moving probe test at that

location, taking care to maintain the small gap (9.5 mm or

3/8 in) to confirm the leak is of repairable size. Use of the

7 g/yr (0.25 oz/yr) position of the detector, after finding an

apparent leak with the 4 g/yr (0.15 oz/yr) setting, may also

be helpful.

G. No. 22791 is sensitive and can take up to 30 seconds to

clear after detecting a small amount of contaminant. It will

typically clear in 2 to 15 seconds.

Caution: Do not use cleaning agents or solvents on or near

A/C lines. Wipe away dirt or potential false-trigger chemicals by

using a dry towel or shop air.