Installation Instructions
AQU126 & AQU243 (Non-Listed)
AQU126, AQU243 (Non Listed) Instructions Doc.# 500-33030 Rev. B
Page
6 of 6
AQU243 and AQU126E Supervised Power Supply/Chargers
Installation Guide
The AQU243 and AQU126 Supervised Power Supply/Chargers with standby battery(s) provide an uninterruptible
24vdc or 12vdc power source. The DC output of AQU243 and AQU126 power supply module is not power limited.
Keep ¼” minimum spacing between non power limited and power limited wiring.
1. This installation should be made by a qualified service person, should conform to all local codes and should
comply with The National Electrical Code (or equivalent).
2. Mount the Power Supply in desired location.
3. Connect DC devices to the Output Terminals. Not power limited. Observe polarity.
4. For AQU243EC8 and AQU126EC8 multi-output units connect DC devices to the output terminals on the PDM-
8C board. (-) Negative power is the bottom row of terminals marked common 1 – 8. (+) Positive power is the top
row of terminals marked 1 – 8. These terminals are just under the green status LED’s. Each (+) terminal is
protected with a PTC circuit breaker. Observe polarity. These outputs are Class II Power Limited.
5. The power table below shows the continuous current you may use for each output.
6. Be sure that the total current requirement conforms to the total available output current.
7. Connect AC FAIL alarm contacts. N/O means normally open with AC ON.
8. Connect LOW BAT alarm contacts. N/O means normally open with battery voltage normal.
9. Connect Line voltage, 90 to 260vac and Earth Ground to the 3 position terminal block marked HIGH VOLTAGE.
The Earth Ground terminal is connected to the enclosure and outer heat sink case for safety and EMI filtering.
(L= line), (N=Neutral), and (G=Ground)
10. To reset a tripped PTC Circuit Breaker, you may have to correct fault and remove load for up to 1 minute. This
allows the PTC re-settable fuse to cool and reset to it's normal “ON” condition.
Selection Table
Part number is shown on outside label.
AQU243
AQU126
Power
Supplies
Total
Continuous DC
Amps
Reserved for
Battery(s)
Charging
DCV Output
PDM-8C Power
Limited Class II
Outputs 1-PTC
circuit breakers
Rating
PDM-8C Main
Power Pull
Replacement
Fuse
AC Input Rating
AQU243
3 Amps
300ma
24vdc
None
None
85-260vac
150w
AQU126E
6 Amps
500ma
12vdc
None
None
85-260vac
150w
The DC outputs of the AQU243 and AQU126 are class
II power limited. The output on the AQU243E &
AQU126E is not power limited. Dress wires to keep a
minimum space of .25” between non-power limited and
power-limited circuits.
Enclosure “E”: 14W x 9”H x 3.5”D