D. TEST MODE

This function is intended to simplify the gas valve adjustment. Listed below are the recommended limits on each boiler and combustion
settings. Automatic modulation does not take place when the controller is in test mode, only temperature limitation based on the boiler
central heating set point. The user can increase or decrease the fan speed by pressing either

{S1/-}

or

{S2/+}

.


To activate test mode, press the

{S2/+}

and

{S3/Program}

keys together for 1 second. Once activated, you will see in the display

{Ser}

and the actual fan speed. The measurement of the combustion levels should always be taken at the highest and lowest fan speeds.
After 20 minutes, test mode stops automatically. To exit test mode, press

{S1/-}

and

{S2/+}

together for 1 second.

COMBUSTION SETTINGS ON ALL MODELS

Natural Gas

Propane LP

Fan Speed

low

high

low

High

Carbon Monoxide (CO%)

0

– 20 ppm

70

– 135 ppm

0

– 20 ppm

80

– 150 ppm

Carbon Dioxide (CO

2

%)

8 ½ - 9 ½%

8 ½ - 9 ½%

9 ½ - 10 ½%

9 ½ - 10 ½%

Table 11

– Combustion Settings on All Models

MOD CON FAN SPEEDS

MODEL

IGNITION

MIN

MAX

300

3000

1250

5500

500

3000

1250

6930

850

3000

1500

5400

Table 12

– Fan Speeds

PART 10 – START-UP PROCEDURES FOR THE INSTALLER

A. PROGRAMMING FOR THE INSTALLER

This section describes each parameter the installer can access to customize the settings of the boiler for a particular installation. These
system limits should not be changed by the user. For future reference, it is important to document your settings within this manual after
you program the system parameters.

B. PROGRAM ACCESS

To start, press and hold

{S3}

and

{S4}

simultaneously for three seconds. You will notice the display change to

|000|

. Then, press and

hold

{S1}

until you see

|925|

. (If you go past

|925|

, you can use

{S2}

to decrease the number.) This is the pass code. To confirm that the

pass code is correct, press and hold the

{S3}

key for 1 second. If the pass code is entered incorrectly, the controller program function

will cancel and return to normal operation. If the code is entered correctly, the control will switch off the gas valve and purge fan while
showing a solid

- - -

in the display. The display will then show a

|1|

alternating to

|de|

. This first function verifies that the control is

configured as a boiler.

C. PROGRAM NAVIGATION

Next you will have to press the

{S3}

key to move through each function. To increase or decrease a value, you will need to press either

{S1}

or

{S2}

to change the default values. If there is no key action for 1 minute, the display returns to normal operation. Changes are

effective immediately but not directly stored until the

{S4}

key is pressed down for 3 seconds then the new values are stored. Listed

below are the varieties of functions the installer can program.

The boiler cannot be programmed while there is a call for heat.

NOTE: See Figure 28 to set outdoor reset curve.

DEFAULT

FUNCTION

VALUE

DESCRIPTION

1

|de|

N/A (no change allowed)

2

149

o

F

N/A (no change allowed)

3

180

o

F

Allows the installer to set the maximum domestic water heater delivery temperature.

Range: 95

o

F

to 185

o

F

4

36

o

F

N/A (no change allowed)

5

7

o

F

Allows the installer to change the differential temperature (dh) in the indirect fired water heater (does not apply if used

with mechanical control)

Range: 1

o

F to 18

o

F