Part 7, Gas connections, A. gas piping – HTP 199-55SA User Manual

Page 42: B. gas table, Part 7 – gas connections

Advertising
background image

42

LP-179 REV. 3.21.14

PART 7 – GAS CONNECTIONS

Failure to follow all precautions could result in fire, explosion, severe injury or death!


The gas supply shall have a maximum inlet pressure of less than 14"
water column (350 mm), ½ pound pressure (3.5 kPa), and a minimum of
3.5" water column. The entire piping system, gas meter and regulator
must be sized properly to prevent pressure drop greater than 0.5" WC as
stated in the National Fuel Gas Code. This information is listed on the
rating plate.

It is very important that you are connected to the type of gas as noted on
the rating plate: "LP" for liquefied petroleum, propane gas, or "Nat" for
natural or city gas. All gas connections must be approved by the local
gas supplier or utility, in addition to the governing authority, prior to
turning the gas supply on.

Do not remove the adaptor in

Figure 24

! It is mandatory that this fitting is

used for connection to a field fabricated drip leg per the National Fuel
Gas Code. You must ensure that the entire gas line to the connection at
the water heater is no smaller than ¾".

Once all inspections have been performed, the piping must be leak
tested. If the leak test requirement is a higher test pressure than the
maximum gas inlet pressure, you must isolate the heater from the gas
line to continue leak testing. To do this, you must turn off the factory and
field-installed gas cocks. This will minimize the possibility of damaging
the gas valve. Failure to do so may damage the gas valve. In the event
the gas valve is exposed to a pressure greater than ½ PSI, 14" water
column, the gas valve must be replaced. Never use an open flame (match,
lighter, etc.) to check gas connections.

A. GAS PIPING

Run the gas supply line in accordance with all applicable codes. Locate and
install manual shutoff valves in accordance with local and state
requirements.

B. GAS TABLE

Refer to the table below to size the supply piping to minimize pressure drop
between meter or regulator and unit.

Maximum capacity of pipe in cubic feet of gas per hour for gas pressures of
.5 psi or less and a pressure drop of .3 inch water column.





Nominal Iron

Pipe Size (In.)

Internal

Dia. (In.)

Length of Pipe (Feet)

BTU’s

Per Hour

x

1,000

10

20

30

40

50

60

70

80

90

100

125

150

175

200

¾

.824

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1

1.049

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1 ¼

1.380

1,050

730

590

500

440

400

370

350

320

305

275

250

225

210

1 ½

1.610

1,600

1,100

890

760

670

610

560

530

490

460

410

380

350

320

Table 10

– Source – ANSI Z223.1

It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas
piping must be sized for proper flow and length of pipe to avoid excessive pressure drop. Both the gas meter and the gas regulator
must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is
undersized or in need of service. You can attach a manometer to the incoming gas drip leg by removing the cap. The gas pressure
must remain between 3.5" WC and 14" WC during stand-by (static) mode and while in operating (dynamic) mode at full output.

Figure 24

– Phoenix Gas Connection - LP-179-Q

Advertising
This manual is related to the following products: