LOGIC
5-279
Chapter 5
●State monitor outputs: Y14 to Y16
State monitor outputs are used to output the internal state of SafetyOne.
State
Intended outputs
(Terminal names)
Initial
Run
Configuration
Protection
Stop
State monitor output 1
(Y14)
■
ON
□
OFF
□
OFF
□
OFF
■
ON
State monitor output 2
(Y15)
■
ON
□
OFF
■
ON
■
ON
■
ON
or□
OFF
State monitor output 3
(Y16)
□
OFF
■
ON
□
OFF
□
OFF
□
OFF
Refer to “Chapter 4 BASIC OPERATIONS” and to “Chapter 6 TROUBLE SHOOTING” for details of
each state.
Warning
The monitor outputs are not safety outputs. Do not use these to construct a safety system.
Caution
Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.