EMERGENCY COMBINATION SYSTEM

8

ECS-6216P/S

6. LINK IN/OUT TERMINAL

Connect LINK IN terminal to previous equipment, and connect LINK OUT terminal to next equipment.

Same for all IN/OUT terminals.

7. TERMINATION SWITCH (LOAD/OPEN)

Switch being set for stable data receive/transmit of LINK IN/OUT.
Refer to Equipment Setting and Checking (page 4) for detailed setting methods.
Caution: Communication error may occur if setting is performed incorrectly.

8. UPGRADE TERMINAL (ISP)

Utilized for software upgrades and is not used otherwise.

9. RS-232 SOURCE DEVICE CONTROLLING TERMINAL (EXCLUSIVE FOR ECS-6216P)

Used to control Inter-M source devices (CD, TUNER) with Windows program.

1) Connectable source devices: Inter-M products equipped with RS-232 communication terminal
2) Maximum recommended communication distance is 12M(40 feet).
3) PIN OUT Specification

10. SPEAKER OUT TERMINAL

Connects to each channel’s speaker. It consists of 3-wire type.
1) In PS mode, it is transmitted only through HOT terminal.
2) In ES mode, it is transmitted through both HOT/EM terminals.

PIN NO.

Functions

1

RS-485 Data - A

2

RS-485 Data - B

3

RS-485 Data - Z

4

NA

5

GND

6

RS-485 Data - Y

7

NA

8

NA

Pin No.

1

2

3

4

5

6~9

Purpose

Not Used

Receive

Transmit

Not Used

Ground

Not Used