King electrical mfg. company, Wiring heater, Pic-a-watt – King Electric Model KBP User Manual

Page 2: Circuit sizing table

Advertising
background image

1. Remove wiring compartment cover.

2. Remove one of the knockouts from back of unit.

It is not necessary to remove grill covers.

3. Size service wire to adequately handle Amp load

of heater. Refer to the Circuit Sizing Table for

proper wire size and circuit protection.

4. Connect supply wire to L1 & L2 as shown in the

diagram below.

5. Secure power supply cable with clamps.

6. Connect groundwire to the green pigtail.

7. Reinstall wiring compartment cover.

8. Adjust the heater to the desired position.

WARNING - Before proceeding further

with the installation of this heater, turn off

the power and lock the supply line for the

heater at the main service box.

Wiring Heater

King electrical mfg. company

9131 - 10th Avenue South Seattle Washington 98108

1900•2850•3800•4750•5700

WATTAGES AVAILABLE IN ONE UNIT

KBP2406

240V -1ph

INSTALLATION INSTRUCTIONS

This heater is shipped from the factory wired for

maximum wattage of 5700 Watts at 240 Volts.

To reduce the wattage unplug (disconnect) an

insulated push on terminal and wrap with electrical

tape to prevent the possibility of electrical contact

with other parts.

Field Wattage Selection

1. 5700 Watts factory wired

2. 4750 Watts disconnect terminal A

3. 3800 Watts disconnect terminals A,D

4. 2850 Watts disconnect terminals A,B,D

5. 1900 Watts disconnect terminals A,B,C,D

E - Black Do Not Disconnect (Common)

F - Red Do Not Disconnect

Insulated Push on

Terminal

C

RED

1

2

3

FAN

DELAY

BLACK

950 WATT

950 WATT

ORANGE

BLUE

B

F

A

YELLOW

RED

GRAY

D

F

E

BLACK

#14

E

END VIEW OF ELEMENT SHOWING

QUICK CONNECT TERMINALS

C

D

E Common

950

F

A

B

E Common

950

F

950

950

950

950

950 WATT

950 WATT

950 WATT

LIMIT

BLACK #14

BLACK #14

BLACK #16

1

2

3

4

L2

BLACK

ORANGE #14

RED #14

GRAY #16

PURPLE #16

FAN

Insulated Push on

Terminal

Pic-A-Watt

Metal Sheath Element

Thermostat

Maintenance & Warranty Information:

The high quality and superior design of this heater will provide years of trouble-free performance. Each year

the heater should be checked and cleaned for lint and dust accumulation. We recommend using a soft bristle-

brush such as a paint brush to assist in removing contaminants from the heater. The motor is permanently lu-

bricated and does not need servicing. King Mfg. Company will repair or replace without charge any KBP2406

heater found to be defective or malfunctioning for five years after purchase to the original owner.

950 WATT

Rotary Switch

L1

A

B

OFF ....... L1-0, L2-0

FAN ....... L1-2, L2-4

HEAT...... L1-1, L2-4, L2-3

FAN DELAY

1-3 N.C., 1-2 N.O.

1-2 Closes on Temp Rise

2007KBP2406.indd : 3/08

WATTS BTUH VOLTS

AMPS

1-PHASE

WIRE

SIZE

CIRCUIT

PROTECTION*

AREA COVERED

(sq. ft.** / cubic ft.***)

1900

2850

3800

4750

5700

6484

9727

12969

16211

19454

240

240

240

240

240

8

12

16

20

24

#14 / 2

#14 / 2

#12 / 2

#10 / 2

#10 / 2

15A - 2P

20A - 2P

30A - 2P

30A - 2P

240 / 1920

360 / 2880

480 / 3840

600 / 4800

720 / 5760

15A - 2P

CIRCUIT SIZING TABLE

* Per the National Electric Code heating circuits are considered a continuous load and therefore must be derated

by 20%. For example: a 20 Amp heating circuit can not have more than 16 Amps of load connected. If heater is

operated at 208V it will draw 13% less Amps and produce 25% less wattage.

** Assumes an 8 ft. high ceiling; Use cubic feet to estimate wattage requirement when ceiling is not 8 ft.

*** If area is larger than 720 sq. ft. / 5,760 cubic feet use more than one heater.

BLACK #16

Advertising