Programming parameters – APC Silcon DP300E Series User Manual
Page 20

20
User Guide Silcon DP300E Series 480V 400-500kVA
7OA0004 US rev. 02
4.4
Programming of battery monitor
Action
Display shows
1.
Press
and
simultaneously to open
for password input
2.
Enter password xx xx xx by pressing
3.
Press
or
until
4.
Enter the expected back-up time in min. at
100% ohmic (pf = 1) load, when the inverter
has a mean efficiency of approx. 96%
Press
I.e. 14.0 min.
5.
Press
to store data
6.
Press
or
until
7
Press
to set Ah for battery
8.
Press
to store data
9.
Press
to exit
Installation of new batteries:
When installing new batteries the procedure in section 4.4 MUST be carried out,
otherwise the monitor may give false alarms.
Programming Parameters
Key in password
:
Last selected
parameter
Expected back-up
time [min.]: XXX.X
Expected back-up
time [min.]: 14.0
Data stored
Battery capacity
in [Ah]: XX.X
Battery capacity
in [Ah]: 7.0
Data stored
Normal operation
load power XX%
NOTE:
Only for APC personnel and
certified local APC personnel.