FM-Approved Releasing Devices
Appendix B: Device Compatibility
The PDRP-1002 PN 51135:A 03/11/99
35
Table 7 UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels
Number of
Detectors Per Zone
Model
Det.
ID
Detector Type
Base Model
Base
ID
Standby
Current
(uA)
PDRP-1002/
PDRP-1002E
System Sensor 1400
A
Ionization
n/a
n/a
100
20
System Sensor 1451
A
Ionization
B401B / B406B
A
120
15 / 1
System Sensor 1851DH
A
Ionization
DH1851DC
A
120
15
System Sensor 2400
A
Photoelectric
n/a
n/a
120
15
System Sensor 2400AIT
A
Photo / Isolated
Thermal / Horn
n/a n/a
120
1
System Sensor 2400AT
A
Photo / Thermal / Horn
n/a
n/a
120
1
System Sensor 2400TH
A
Photo / Thermal
n/a
n/a
120
15
System Sensor 2451
A
Photoelectric
B401B / B406B
A
120
15 / 1
System Sensor 2451TH
A
Photo / Thermal
B401B / B406B
A
120
15 / 1
System Sensor 2851DH
A
Photoelectric
DH2851DC
A
120
15
System Sensor 1451DH
A
Ionization
DH-400
A
120
15
System Sensor 2451
A
Photoelectric
DH-400
A
120
15
System Sensor 2300T
A
Photo / Thermal
n/a
n/a
120
15
System Sensor 1800
A
Ionization
n/a
n/a
100
n/a
System Sensor 1851B
A
Ionization
B101B
A
120
n/a
System Sensor 1851B
A
Ionization
B107B
A
120
n/a
System Sensor 2800
A
Photoelectric
n/a
n/a
120
n/a
System Sensor 2800TH
A
Photo / Thermal
n/a
n/a
120
n/a
System Sensor 2851B
A
Photoelectric
B101B
A
120
n/a
System Sensor 2851B
A
Photoelectric
B107B
A
120
n/a
System Sensor 2851BTH
A
Photo / Thermal
B101B
A
120
n/a
System Sensor 2851BTH
A
Photo / Thermal
B107B
A
120
n/a
System Sensor 1151
A
Ionnization
B401 / B110LP /
B116LP
A
120
15 / 15 / 1
System Sensor 2151
A
Photoelectric
B401 / B110LP /
B116LP
A
120
15 / 15 / 1