1 The PDRP-1002/PDRP-1002E

Input Circuits

6

The PDRP-1002 PN 51135:A 03/11/99

1 The PDRP-1002/PDRP-1002E

Features

•

Microprocessor-controlled

•

Power-limited on all circuits except Municipal Box output

•

Alarm and trouble resound

•

Four Class A (Style D)/Class B (Style B) Initiating Device Circuits

•

Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits

•

Two Class B (Style Y) Release Circuits

•

General alarm and trouble relays

•

Optional module for 4 zone/function relays (4XZM)

•

Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm systems

•

Optional volt/amp meter module (4XMM)

•

Optional supervised remote annunciator (RZA-4X)

•

Requires LED Interface Module (4XLM)

•

Optional digital communicator (NOTI•FIRE 911AC)*

•

Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems

•

Supervisory Input Option

•

Delay timer (adjustable)

•

Three abort function options

•

Designed for suppression standards NFPA 12, 12A and 12B

•

Disable/enable controls per initiating zone

•

Last Event Recall

•

Battery/Earth fault supervision

•

Fuse protection on all Notification/Release Circuits

•

RMS regulated output power, 2.25 amps

•

7 amp/hour to 15 amp/hour battery options, up to 90 hours standby

•

Resettable and non-resettable regulated power outputs

•

Extensive transient protection

•

Watchdog timer to supervise microprocessor

•

Output circuits protected against false activations

•

Slide-in zone identification labels

•

Steel cabinet 14.5 in (368.3 mm) wide by 16 in ( 406.4 mm) high by 5 in (127 mm)
deep

•

Dead-front dress panel option (DP-4X)

•

Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)

•

Abort and manual release circuits

•

Cross-zone option

*

Applications which require the NOTI•FIRE 911AC are not FM approved

.

Circuits

Input Circuits

Detector Zone 1, Class A (Style D)/Class B (Style B)
Detector Zone 2, Class A (Style D)/Class B (Style B)
Abort, Class A (Style D)/Class B (Style B)
Manual Release, Class A (Style D)/Class B (Style B)

Output circuits (optional auxiliary relays track these four circuits)

Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y)
Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Releasing Circuit 2, Class B (Style Y)/Supervisory Input, Class B (Style B)