Iq3xcite installation instructions, 3 installation - mounting, Connect i/o bus – TREND IQ3xcite User Manual

Page 6: Terminate i/o bus, L+ l- l- l n dc adj. in

Advertising
background image

6

IQ3xcite Web Enabled Controller Installation Instructions TG200626 Issue 2 21/04/08

IQ3xcite

Installation Instructions

Connect I/O Bus

(continued)

13

L+

L+

L-

L-

L

N

DC

ADJ.

IN

PSR

L+

L+

L-

L-

L

N

DC

ADJ.

IN

PSR

type B

type A

type B

terminator

24 Vdc

PSU

+24 Vdc

0 V

Data Hi

Data Lo

+24 Vdc

0 V

Data Hi

Data Lo

Ground

Ground

White

Blue
Black

Black

Red

1
2
3
4

5

5
4
3
2

1

c

continued

Fully screened and bonded contiguous multi section cabinet

Check IQ3xcite 24 Vdc
combined supply
current availability

An additional 24 Vdc ±15% power supply must be used to supply the IO modules if:

• There are more than 6 I/O modules (excluding /8AO, /4AO, /16DI, /8DI, /8DI/8TI, /8DO/HOA, /4DO/HOA, and /8DO
serial number >= M3D8 C0 508 1136, /4DO serial number >=M3D4 C0 508 012; which do not need to be included
in the count).

or

• The main controller 24 Vdc combined supply would be overloaded

L+

L+

L-

L-

L

N

DC

ADJ.

IN

Black

Red

Black

White

Blue

PSR

1
2
3
4

5

L+

L+

L-

L-

L

N

DC

ADJ.

IN

Black

Red

Black

White

Blue

PSR

5
4
3
2

1

PSR connection to left side

PSR connection to right side

230 Vac input
power supply

Trend can supply the PSR range of DIN rail mounted auxiliary power supplies (e.g. 1.3 A or 2.5 A). They have isolated outputs.

d

Close flap

3 Installation - Mounting

(continued)

XCITE/PCON/1000, 1 metre cable (type A)
available, order separately

24 Vdc

PSU

+24 Vdc

0 V

Data Hi

Data Lo

+24 Vdc

0 V

Data Hi

Data Lo

Ground

Ground

White

Blue
Black

Black

Red

1
2
3
4

5

5
4
3
2

1

XCITE/PCON/50, for adjacent
modules available, order separately
(modules separated by 10 mm)

IQ3 Configuration Manual TE200768

External PSU with isolated output

External PSU with isolated output

WARNING: External PSU must have isolated output and
comply with relevant EMC and safety standards

Note that the maximum current that can be flow through an I/O module using the 24 Vdc and 0 V terminals, from one module to the
next, is 2.5 A.

Terminate I/O Bus

14

on furthest I/O module or on controller if no I/O modules

b

a

Open flap

Plug in terminator (supplied)

c

Close flap

XCITE/TERM terminator
(supplied with IQ3xcite)
(XCITE/TERM/5,
pack of 5 available separately)

230 Vac input
power supply