TW/S
Installation Instructions
TW/S Wireless Space Temperature Sensor Installation Instructions TG200781 Issue 1/C 25/04/07
2
INSTALLATION
(continued)
Requirements
(continued)
2
h
H O
2
-10 °C
-14 °F
+50 °C
+122 °F
0 %RH
90 %RH
-30 °C
-22°F
+110 °C measurement
+230 °F
j
k
i
Mount backplate
4
wall
wall box
Remove backplate
3
a
b
60 mm (2.36”)
35 mm (1.38”)
35 mm (1.38”)
FR
ABS
l
Protection: IP20
• Avoid using many other devices on frequency
range 433.05 to 434.79 MHz
• Keep away from sources of interference (e.g.
computer >1 m (3 yds), microwave ovens,
switch mode power supplies).
• Mount above partition height if possible.
TW/S
XW/R/IQ
75 m (82 yds)
(maximum)
Note that range may be affected
by environmental characteristics,
e.g. partitions, walls, building
structure etc.