Operation powerrail303 page 4 – TREND EM3_CT_N User Manual

Page 6

Advertising
background image

Operation

PowerRail303

Page 4

2.4 Instantaneous kW Display

Press

144.00

kW

Instantaneous Power

2.4.1 REV CT

The instantaneous power display may show negative values indicating export power or incorrectly
wired inputs. REV CT will also be shown indicating that the most likely cause of the negative
reading is one or more current transformers fitted the wrong way round on the primary conductor.

2.5 kW Demand Display (Option)

Press

Demand

100.00

kW

kW Demand

KW demand is only available on meters factory fitted with this option. If the user sets a demand
period of N minutes (eg 30 minutes) the display will be updated every N seconds (eg every 30
seconds). The display shows the average of all kW readings taken over the most recent demand
period (eg average over 30 minutes). This average kW parameter is commo nly known as kW
Demand.

Press

Pk Demand

150.00

kW

Peak kW Demand

Peak KW demand is only available on meters factory fitted with the demand option. The display
shows the largest value of kW demand recorded since the user last reset it. The peak kW
Demand value is stored during power loss to the meter.

2.5.1 Resetting Peak kW Demand

To reset Peak kW Demand, press

and

, for approximately 2 seconds, while displaying

Peak kW Demand.