Programming

PowerRail303

Page 7

3 Programming

3.1 Programming Menu

To enter programming mode: Hold

and

together for 5 Seconds.

The first programmable parameter, CT Primary, is displayed.

3.1.1 CT Primary Programming

Setup

CT 200


This should be set to match the nominal primary current rating, in Amps, of the external current
transformers (CTs) fitted to the meter. The CT secondaries must match the nominal input rating of
the meter (5A on standard meters).

Press the up key

or down key

to select CT values from a table of standard primary

currents.

Press

when the desired value is set to move to the next parameter.

For primary currents not found in the standard table use fine adjust.

To enter/exit Fine Adjust mode, press

and

together for two seconds.

3.1.2 Nominal Primary Current Programming

Setup

CTf 190


Press the up key

or down key

to increase/decrease the CT primary setting in steps of

10A.

Press

when the desired value is set to move to the next parameter.

3.1.3 Nominal Voltage Programming

Setup

Un 400


If no external Potential Transformer (PT) is fitted this is must be set to match the nominal line-line
voltage (Un) of the meter as detailed on its rating label.

If an external PT is fitted this should be set to match the PT nominal primary line-line voltage rating,
in volts. The PT secondary must match the nominal input rating of the meter (eg 110V L-L).

Press the up key

or down key

to select values from a table of standard PT primaries.

Press

when the desired value is set to move to the next parameter.